Tuncmatik PowerUp One PF 1 6K User Manual

Online ups

Advertisement

Quick Links

User Manual
PF 1 6K/10K Online UPS
Uninterruptible Power Supply System
Version: 1.4

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PowerUp One PF 1 6K and is the answer not in the manual?

Questions and answers

Summary of Contents for Tuncmatik PowerUp One PF 1 6K

  • Page 1 User Manual PF 1 6K/10K Online UPS Uninterruptible Power Supply System Version: 1.4...
  • Page 2 Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.
  • Page 3: Table Of Contents

    Table of Contents 1. SAFETY AND EMC INSTRUCTIONS ........................... 1 1-1. T ..........................1 RANSPORTATION AND TORAGE 1-2. P ................................1 REPARATION 1-3. I ................................1 NSTALLATION 1-4............................ 2 ONNECTION ARNINGS 1-5. O ................................... 3 PERATION 1-6. S .................................. 3 TANDARDS 2.
  • Page 4: Safety And Emc Instructions

    1. Safety and EMC instructions Please read carefully the following user manual and the safety instructions before installing the unit or using the unit! 1-1. Transportation and Storage Please transport the UPS system only in the original package to protect against shock and impact.
  • Page 5: Connection Warnings

    1-4. Connection Warnings • In accordance with safety standard EN-IEC 62040-1, installation has to be provided with a《Backfeed Protection》 system, as for example a contactor, which will prevent the appearance of voltage or dangerous energy in the input mains during a mains fault. There is no standard backfeed protection inside of the UPS.
  • Page 6: Operation

    • Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
  • Page 7: Installation And Operation

    2. Installation and Operation There are two different types of online UPS: standard and long-run models. Please refer to the following model table. Model Type Model Type standard model Long-run model 10KL We also offer optional parallel function for these two types by request. The UPS with parallel function is called as “Parallel model”.
  • Page 8: Single Ups Installation

    2-3. Single UPS Installation Installation and wiring must be performed in accordance with the local electric laws/regulations and execute the following instructions by professional personnel. Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the hazards of electric shock or fire.
  • Page 9: Ups Installation For Parallel System

    ● Make sure the UPS is not turned on before installation. The UPS should not be turned on during wiring connection. ● Do not try to modify the standard model to the long-run model. Particularly, do not try to connect the standard internal battery to the external battery.
  • Page 10: Software Installation

    Parallel communication port connection Share current cable connection Diagram 2: Communication cable connection Diagram 1: Power cable connection Wiring diagram of parallel system 2-5. Software Installation For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown.
  • Page 11: Operations

    3. Operations 3-1. Button Operation Button Function  Turn on the UPS: Press and hold the button more than 0.5s to turn on the UPS. ON/Enter Button  Enter Key: Press this button to confirm the selection in setting menu. ...
  • Page 12 LCD Panel: Display Function Backup time information Indicates battery discharge time in numbers. H: hours, M: minutes, S: seconds Fault information Indicates that the warning and fault occurs. Indicates the fault codes, and the codes are listed in details in section 3-9. Mute operation Indicates that the UPS alarm is disabled.
  • Page 13: Audible Alarm

    3-3. Audible Alarm Description Buzzer status Muted UPS status Bypass mode Beeping once every 2 minutes Battery mode Beeping once every 4 seconds Fault mode Beeping continuously Warning Overload Beeping twice every second Others Beeping once every second Fault Beeping continuously 3-4.
  • Page 14 total loads connected to the UPS less than 80% of its nominal power capacity to prevent overload for system safety. 5) If the overload time is longer than acceptable time listed in spec at AC mode, the UPS will automatically transfer to Bypass mode. After the overload is removed, it will return to AC mode. If the overload time is longer than acceptable time listed in spec at Battery mode, the UPS will become fault status.
  • Page 15 2) In Bypass mode, output voltage of the UPS is still present. In order to cut off the output, switch off the input breaker. A few seconds later, there is no display shown on the display panel and UPS is complete off.
  • Page 16: Parallel Operation

    external battery connection. (Normal UPS shutdown means turning off input breaker in bypass/no output mode). 3-5. Parallel Operation 3-5-1. Parallel system initial startup First of all, please make sure all of the UPSs are parallel models and have the same configuration. 1) Turn on each UPS to AC mode respectively (Refer to section 3-4-1).
  • Page 17: Abbreviation Meaning In Lcd Display

    First method: 1) Press the “OFF” key twice and each time should last for more than 0.5s. Then, the UPS will enter into bypass mode without output. 2) Turn off the output breaker of this unit, and then turn off the input breaker of this unit. 3) After it shuts down, you can turn off the battery breaker (for long-run model) and remove the parallel cable and share current cable.
  • Page 18: Lcd Setting

    3-7. LCD Setting Parameter 1 Parameter 2 There are two parameters to set up the UPS. Parameter 1: It’s for program alternatives or setting options. Refer to below table. Parameter 2 is the setting values for each program. Programs available list for parameter 1: Bypass/ Battery Code...
  • Page 19  02: Output frequency Interface Setting 60 Hz, CVCF mode Parameter 2: Output Frequency Setting the output frequency. You may choose following three options in parameter 2: 50CF: Setting UPS to CVCF mode and output frequency will be fixed at 50Hz. The input frequency could be from 46Hz to 64Hz. 60CF: Setting UPS to CVCF mode and output frequency will be fixed at 60Hz.
  • Page 20  04: Frequency range for bypass Interface Setting Parameter 1 & 2: Setting acceptable frequency range for bypass mode. You have to set up the range by setting high and low points. When it shows “LLS” in parameter 2, please press “Enter”...
  • Page 21  07: Frequency range for ECO mode Interface Setting Parameter 1 & 2: Setting acceptable frequency range for ECO mode. You have to set up the range by setting high and low points. When it shows “LLS” in parameter 2, please press “Enter” key and it will show “LS”...
  • Page 22  10: Reserved Interface Setting Reserved  11: Reserved Interface Setting Reserved  12: Hot standby function enable/disable Interface Setting Parameter 2: HS.H Enable or disable Hot standby function. You may choose following two options in Parameter 2: YES: Hot standby function is enabled. It means that the current UPS is set to host of the hot standby function, and it will restart after AC recovery even without battery connected.
  • Page 23  14: Charger voltage adjustment Interface Setting After it shows “14” in parameter 1, please press “Enter” key first. Then, you may choose Ad or SU to adjust charger voltage in parameter 1 by pressing “Up” or “Down” key. After pressing “Enter”...
  • Page 24: Operating Mode/Status Description

     17: Charging current setting Interface Setting Parameter 1: Set the charging current of the charger at 1A, 2A, 3A or 4A (001 ~ 004). Parameter 2: Calibrate the charging current. If there is deviation between setting current and real measured current, please use this parameter to calibrate the charging current.
  • Page 25 ECO mode Description When the input voltage is within voltage regulation range and ECO mode is enabled, UPS will bypass voltage to output for energy saving. LCD display CVCF mode Description When input frequency is within 46 to 64Hz, the UPS can be set at a constant output frequency, 50 Hz or 60 Hz.
  • Page 26 LCD display When UPS is in AC mode or CVCF mode, press “Test” key for more than Battery Test Description 0.5s. Then the UPS will beep once and start “Battery Test”. The line between I/P and inverter icons will blink to remind users. This operation is used to check the battery status.
  • Page 27: Fault Code

    3-9. Fault Code Fault event Fault code Icon Fault event Fault code Icon Bus start failure None Battery SCR short circuited None Bus over None Inverter relay short circuited None Bus under None Charger short circuited None Bus unbalance None Can communication fault None Inverter soft start failure...
  • Page 28: Trouble Shooting

    4. Trouble Shooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause Remedy No indication and alarm in the front The AC input power is not Check if input cable firmly display panel even though the mains is connected well.
  • Page 29: Storage And Maintenance

    5. Storage and Maintenance 5-1. Storage Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table: Storage Temperature Recharge Frequency Charging Duration -25°C - 40°C Every 3 months...
  • Page 30: Specifications

    6. Specifications MODEL 10KL CAPACITY* 6000 VA / 6000 W 10000 VA / 10000 W INPUT 110 VAC(L-N) ± 3 % at 0-60% Load Low Line Loss 176 VAC(L-N) ± 3 % at 60%-100% Load Voltage Range Low Line Comeback Low Line Loss Voltage + 10V High Line Loss 300 VAC(L-N) ±...

Table of Contents