Safety Statements; General Instructions - Emerson Copeland YB56K1G Application Manuallines

Scroll compressors for r290 applications
Table of Contents

Advertisement

1.2

Safety statements

▪ Refrigerant compressors must be employed only for their intended use. The system has
to be labelled according to the applicable standards and legislation.
▪ Only qualified and authorized RACHP (refrigeration, air conditioning and heat pump)
personnel are permitted to install, commission and maintain this equipment. Only
competent personnel (as specified in EN 13313) qualified for flammable refrigerant
handling is permitted to commission, initiate and maintain the compressor/refrigeration
systems using flammable refrigerant; non-trained personnel, including the user, are not
allowed to do so and must call on an expert.
▪ When planning and building systems, a risk assessment and corresponding precautions
for risk mitigation must be taken by the system designer. Special attention must be paid
to flammability when dealing with A3 refrigerants.
▪ The maximum refrigerant charge is specified in standards such as, but not limited to
EN 378, EN 60335-2-40 and EN 60335-2-89. The system designer shall implement all safety
measures defined by the applicable standards and the maximum refrigerant charge shall
not be exceeded.
▪ If a flammable atmosphere is detected, immediately take all necessary precautions to
mitigate the risk as determined in the risk assessment.
▪ Electrical connections must be made by qualified electrical personnel.
▪ All valid standards for connecting electrical and refrigeration equipment must be
observed.
▪ The national legislation and regulations regarding personnel protection must be observed.
1.3

General instructions

WARNING
Pressurized
breakdown! Accidental system start before complete set-up must be avoided.
Never leave the system unattended without locking it out electrically when it is
under vacuum and has no refrigerant charge, when it has a holding charge of
nitrogen, or when the compressor service valves are closed.
WARNING
System breakdown! Personal injuries! Only approved refrigerants and
refrigeration oils must be used.
WARNING
High shell temperature! Burning! Do not touch the compressor until it has
cooled down. Ensure that other materials in the area of the compressor do not
come into contact with it. Lock and mark accessible sections.
CAUTION
Overheating! Bearing damage! Do not operate compressor without
refrigerant charge or without it being connected to the system.
CAUTION
Contact with refrigerant oil! Material damage! Polyalkylene glycol (PAG)
lubricant must be handled carefully and the proper protective equipment
(gloves, eye protection, etc.) must be used at all times. Refrigerant oil must
not come into contact with any surface or material that it might damage,
including, without limitation, certain polymers, eg, PVC/CPVC and
polycarbonate.
IMPORTANT
Transit damage! Compressor malfunction! Use original packaging. Avoid
collisions and tilting.
2
Use personal safety equipment. Safety goggles, gloves, protective
clothing, safety boots and hard hats should be worn where necessary.
system!
Serious
personal
injuries
and/or
system
AGL_Ref_ST_YBK1G_EN_Rev01

Advertisement

Table of Contents
loading

This manual is also suitable for:

Copeland yb64k1gCopeland yb81k1gCopeland yb97k1g