BEFORE INSTALLING THE WIRED CONTROLLER
•
This manual provides instructions for installing the wired
CAUTION
controller. Please refer to the wiring diagram of this installation
manual for connecting the wired controller with indoor unit.
•
The wired controller operates in a low voltage loop circuit.
Strictly DO NOT directly contact the high voltage cable
above, such as 115V,220V,380V. DO NOT allow the controller
or controller loom to come in contact with high voltage cables
such as 115V and above. Clearances for this situation shall
be 300mm or more.
•
The shielded wire of the wired controller must be grounded
firmly.
•
After completing the wire controller connection, DO NOT use
Megger tester to check the insulation. That may damage the
product.
A maximum of two controllers may be installed on a system and
the mix may contain any of the following three controllers:
NOTE
CNTRLDRCINW / CNTRLDRCIPW / CNTRLDRCIPB