NO.
Code
System high-pressure protection or discharge
temperature protection
21
P0
System low pressure protection
22
P1
Tz/7 Coil final outlet temperature too high
23
P2
T4 ambient temperature too high in cooling mode
24
P3
System A current protection
25
P4
System B current protection
26
P5
Inverter module failure
27
P6
High temperature protection of system condenser
28
P7
Water inlet and outlet temperature difference protection
30
P9
Water inlet and outlet temperature difference anomaly protection
31
PA
Antifreeze protection in winter
32
Pb
Evaporator pressure too low in cooling
33
PC
Cooling evaporator low temperature antifreeze protection
35
PE
T4 ambient temperature too high in heatling mode
37
PH
Content
36
Note
Occurs 3 times in 60 minutes and
the error can be recovered by
turning off the power supply only
Occurs 3 times in 60 minutes and
the error can be recovered by
turning off the power supply only
Recovered upon error recovery
Recovered upon error recovery
Occurs 3 times in 60 minutes and
the error can be recovered by
turning off the power supply only
Occurs 3 times in 60 minutes and
the error can be recovered by
turning off the power supply only
Recovered upon error recovery
Occurs 3 times in 60 minutes and
the error can be recovered by
turning off the power supply only
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery