Download Print this page

Midea MC-SU60-RN1L Operation Manual page 16

Hide thumbs Also See for MC-SU60-RN1L:

Advertisement

DOUBLE SETPOINT
DOUBLE SETPIONT
DISABLE
OK
Press the "▲" and "▼" buttons to select the
ENABLE or DISABLE, and press the "OK"
button to save the setting.If setting the
DISABLE then return to the previous
interface.If setting the ENABLE then enter the
interface as follows:
DOUBLE SETPOINT
SET
SET
POINT
POINT
COOL_1
COOL_1
HEAT_1
7℃
35 ℃
ok
SET
SET
POINT
POINT
COOL_2
HEAT_2
7℃
30℃
Operation instructions:
Press the "◄" and "►" buttons to select
setpoint mode, press the "▲" and "▼" buttons
to set the parameter value,and press the "OK"
button to save the setting and return to the
previous interface,or press the "BACK" button
to cancel the setting and return to the previous
interface.
The main control board detects if the port
"TEMP-SW"is closed,and if the port is closed
the units will run according to the temperature
of "SET POINT COOL_2" or "SET POINT
HEAT_2",other wise ,the units run according
to the temperature of "SET POINT COOL_1"
or "SET POINT HEAT_1".
Temperature compensation:
Press the "▲" and "▼" buttons to select
"TEMPERATURE COMPENSATION" in the
"USER MENU" interface, and press the "OK"
button to enter the interface. The interface
display is as follows:
TEMP COMPENSATION
OK
12
COOL MODE
HEAT MODE

Advertisement