Available languages

5.2.1. Start-stop control
Single-wire pulse start/stop
Enable the Pulse Auto Start/Stop Function by set P2-03=1 first then define a terminal function to Pulse
Run (DI function 13 or 14). With below wiring, the single wire pulse start/stop function can be
achieved.
Two-wires mode 1 (factory default)
The DI terminal FWD is default to forward run function, and the DI terminal REV is default to reverse
run function. You can achieve the two wires start/stop function by Wiring and parameters set as below.
EN
Two-wires mode 2
In this mode, the FWD terminal is to start/stop the motor, the REV terminal is to control the running
direction. The function can work with Wiring and parameters set as below.
Three-wire mode 1
The DI terminals FWD and REV are used to start the motor by pulse for different direction, the DI1
terminal is used to stop the motor. The function can be achieved by wiring and parameter set as below.
36