Note: Other fuel can also be used, such as LPG and Hydrogen 5. SSA80 Series Burner Description SSA80 series of burners are the patented products of Anderson Thermal Solutions (Suzhou) Co., Ltd. Designed for the industry kiln as high-performance burner. The burner has the character of high flame rigidity and low emission of nozzle mix burner.
Anderson Thermal Solutions – SSA80 Operation Manual structure, fuel and combustion air go through respective orifice to the mixing chamber to make multi-stage mixture, Producing strong hot gas flow to penetrate the object to be heated to get uniform temperature. This can keep product quality and heating efficiency. Extremely low NO the emissions.
SiC tube in high temperature application. 7. Burner Operation Data Following table 1 shows the SSA80 series burner operation data. (unit: mm), below data based on Natural gas, high velocity combustor and atmosphere air. Table 1: SSA80 series of burner operation data.
Anderson Thermal Solutions – SSA80 Operation Manual 8. Performance Curves The operation and emission curves of the SSA80 series burner is shown in Figures 2 and 3. Fig 2. SSA80 Series Burner Operation Zone Fig3. SSA80 Series Burner Emission 9. Burner Installation Dimension Diagram Following Fig 4 shows the SSA80 burner installation dimension.
Anderson Thermal Solutions – SSA80 Operation Manual 10.4 Environment Be sure the burner operating environment matches the original operating specifications. Check the following items – Voltage, frequency, and stability of electrical power – Fuel type and fuel supply pressure – Adequate fresh, clean, combustion air –...
10.8 Burner commission Special attention: The SSA80 Series burners, described herein, are designed to mix fuel with air. All fuel burning devices are capable of producing fires and explosions, if improperly applied, installed, adjusted, controlled, or maintained. Do not bypass any safety feature; fire or explosion could result.
Anderson Thermal Solutions – SSA80 Operation Manual from the appropriate SSA80 burner table to set the differential air pressure needed at high fire. Set the system to low fire air. Drive to low fire position. Measure pressure with manometer set to 0.5mbar. This is the initial setting only. Further adjustment may be required.
If necessary, the frequency of audit should be increased. Leak detection, control functions of the equipment must be included in the scope of audit. Only Anderson technicians or those who are been trained and qualified by Anderson, as well as other relevant professionals, can maintain the burners.
Anderson Thermal Solutions – SSA80 Operation Manual 12. Troubleshooting Procedures Problem Possible Cause Solution Check air pressure switch adjustment. Cannot initiate a start Air pressure switch has not made contact sequence Check air filter. Check blower rotation. Check outlet pressure from blower.
Page 14
Anderson Thermal Solutions – SSA80 Operation Manual Too much gas: Gas pressure out of the Check start-up setting. If necessary, main gas pressure regulator is too high remove regulator and investigate. Not enough gas: The gas pressure out Check start-up setting. Check...
Anderson Thermal Solutions – SSA80 Operation Manual 13. Appendix 13.1 Operation Manual Record Each trained person must verify that he has read and understood the contents of the operating manual and know how to operate and maintain this series of burners correctly.
Anderson Thermal Solutions – SSA80 Operation Manual 13.2 Half Year Audit Record Routine audit must be made every 6 months. Please sign the following table. Function Audit Date Inspector Problem description Next Audit Time Flame sensor state Air and gas pressure...
Page 17
Anderson Thermal Solutions – SSA80 Operation Manual Attention: Safety audit is prohibited when burner is running, otherwise, accident could be caused! If you have any questions. Please call us or send an e-mail to get more information Our telephone no. is +86 (512) 6592 4663...
Need help?
Do you have a question about the SSA80 and is the answer not in the manual?
Questions and answers