Machines With A Fan; Machines Without A Fan (Optional) - Siemens 1FP1/3 Operating Instructions Manual

Table of Contents

Advertisement

3.3.1.2

Machines with a fan

Self-ventilation (standard): Cooling method IC 411 according to EN / IEC 60034-6
Located at the ND end of the stator housing is an air intake cowl that guides the external air on
its way to the motor. The external air is drawn in through openings in the air intake cowl and
flows axially across the outer cooling ribs of the motor frame. The fan wheel for the external
flow of cooling air is attached to the machine shaft.
The fan wheels are bidirectional.
Check the cooling effect below rated speed in the case of frequent switching or braking – or if
the speed is controlled continually below the rated speed.
Forced ventilation (optional): Type of cooling IC 416 in accordance with EN / IEC 60034-6
Cooling that does not depend on the speed is achieved by means of a unit that is independent
of the motor operating state (forced ventilation). This unit is closed to the outside by a fan cover.
It has its own main drive with fan impeller which creates the cooling air flow required for cooling
the motor.
3.3.1.3

Machines without a fan (optional)

Surface cooling by free convection: Cooling method IC 410 according to EN / IEC 60034-6
IC410
Figure 3-1
1LE1, 1FP1/3, 1PC1/3 shaft height 63 ... 315
Operating Instructions, 11/2023, A5E38483075A
IC4A1A0
IC410
Description