M-system R7HL-TS4 Instruction Manual page 3

Thermocouple input module, 4 points (high-speed link system)

Advertisement

■ NETWORK, POWER SUPPLY TERMINAL ASSIGNMENT
• Full-duplex communication
4
5
RXD+
RXD– +24V 0V
1
2
TXD+ TXD– FG
NO.
ID
1
TXD+
Network (slave, transmission +)
2
TXD–
Network (slave, transmission –)
3
FG
4
RXD+
Network (master, transmission +)
5
RXD–
Network (master, transmission –)
6
+24V
7
0V
• Half-duplex communication
4
5
+
– +
TR
TR
1
2
NC
NC
NO.
ID
1
NC
2
NC
3
FG
4
TR+
5
TR–
6
+24V
7
0V
PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R7CON for detailed operation.
■ CHANNEL INDIVIDUAL SETTING
PARAMETER
TC Type
Temp Unit
Zero scale
Full scale
Bias
Gain
Zero temp
Full temp
■ CHANNEL BATCH SETTING
PARAMETER
Conversion rate
SEN TRONIC
6
7
3
FUNCTION, NOTES
FG
Power input (24V DC)
Power input (0V)
6
7
24V
0V
3
FG
FUNCTION, NOTES
No connection
No connection
FG
Network
Network
Power input (24V DC)
Power input (0V)
AVAILABLE RANGE
K (CA)
E (CRC)
J (IC)
T (CC)
B (RH)
R
S
C (WRe 5-26)
N
U
L
P (Platinel II)
(PR)
C, F, K
-32000 to +32000
-32000 to +32000
-320.00 to +320.00
-3.2000 to +3.2000
Depends on sensor type
Depends on sensor type
AVAILABLE RANGE
0: 250 msec.
1: 500 msec.
056 222 38 18
AG
■ INPUT TERMINAL ASSIGNMENT
10
11
12
13
+IN0
–IN0
+IN1
1
2
3
4
+CJ0
–CJ0
+CJ1
–CJ1
NO.
ID
FUNCTION
1
+CJ0
CJC 0
2
–CJ0
CJC 0
3
+CJ1
CJC 1
4
–CJ1
CJC 1
5
NC
No connection
6
+CJ2
CJC 2
7
–CJ2
CJC 2
8
+CJ3
CJC 3
9
–CJ3
CJC 3
DEFAULT SETTING
K (CA)
C
0
10000
0.00
1.0000
0.00 (degC)
0.00 (degC)
DEFAULT SETTING
0: 250 msec.
mailbox@sentronic.com
www.sentronic.com
R7HL-TS4
14
15
16
17
18
–IN1
NC
+IN2
–IN2
+IN3
–IN3
5
6
7
8
9
NC
+CJ2
–CJ2
+CJ3
–CJ3
NO.
ID
FUNCTION
10
+IN0
T/C + 0
11
–IN0
T/C – 0
12
+IN1
T/C + 1
13
–IN1
T/C – 1
14
NC
No connection
15
+IN2
T/C + 2
16
–IN2
T/C – 2
17
+IN3
T/C + 3
18
–IN3
T/C – 3
EM-7812-B Rev.5 P. 3 / 5