Parameters
5.4 Explanation of the module/channel parameters
Information on the measuring ranges and the display with disabled or enabled failure
monitoring can be found in the section "Analog value display (Page 85)".
• If failure monitoring is enabled, the following applies to the measuring range:
3.6 mA < valid measuring range (nominal range) < 21 mA
– Hysteresis at the upper end of the measuring range (detection "Overflow/nominal
– Hysteresis at the lower end of the measuring range (detection "Underflow/nominal
• Diagnostics for enabling failure monitoring
You can enable a diagnostic message for the overflow/underflow (Diagnostics overflow/
Diagnostics underflow).
If you enable wire break and underflow diagnostics simultaneously, the wire break
diagnostic is output.
5.4.9
Diagnostics HART
Definition
Enabling the diagnostics of the HART frame-specific monitoring and the status information
supplied by the connected field device in the HART frame (HART device status).
The HART diagnostics are reported as maintenance events.
Maintenance events (Page 65)
5.4.10
Diagnostics overflow
Definition
Enabling of the diagnostics for overrange.
5.4.11
Diagnostics underflow
Definition
Enable diagnostics for underrange.
28
range"):
- The analog value is invalid as of 21 mA.
- The analog value becomes valid again when it falls below the value 20.5 mA.
range"):
- The analog value is invalid as of 3.6 mA.
- The analog value becomes valid again when it rises above the value 3.8 mA.
AI 4xI 2-/4-wire HART ISOL HA
Equipment Manual, 07/2022, A5E50101523-AB