A.3 Parameter assignment and structure of the HART mapping parameters
Figure A-3
A.3
Parameter assignment and structure of the HART mapping
parameters
Structure of data record 130
Data record 130 has a total length of 12 bytes.
You can use the parameters of data record 130 to configure/map up to 4 HART variables of the
individual channels in the input address space of the I/O module, provided you have selected
configuration with HART variables in the input area, see section Configuration options (Page 21).
62
Structure of byte x to x+n for channels 0 to 3
AI 4xI 2-/4-wire HART ISOL HA
Equipment Manual, 07/2022, A5E50101523-AB

Advertisement

Table of Contents
loading