14 - ELECTRICAL CONNECTIONS
General fault alarm:
Connector
1
2
J3 (CPU)
Remote control: Connect the unit's general fault reporting or alarm 
to the terminals on the unit's terminal strip (see wiring diagram).
• Output specification: 2 A sous 250 V.
Automatic operation control:
Connector
1
2
3
J6 (CPU) 
CA
Remove shunt "CA" from between the terminals on the unit terminal 
strip  (see  wiring  diagram)  and  connect  a  "C1"  contact  to  these 
terminals (high-quality polarity-free contact).
• Contact open → unit off
• Contact closed → unit authorised to run
• Input specification: 24 V - 15 mA.
Display of the operating state of pump No. 1
Connector
1
2
3
J5 (CPU) 
• Contact open → Pump off
• Contact closed → Pump in operation
• Input specification: 24 V - 15 mA.
Other connections can be made to the CPU board
Water pump control
Connector
1
2
J3 (CPU) 
Connect the supply to the pump relays between the terminals of 
the connector on the main board.
• Output specification: 2 A under 250 V
Setpoint 1/setpoint 2 selector control
Connector
1
2
3
J6 (CPU) 
Connect a "C2 " contact to the connector on the CPU board (high-
quality polarity-free contact)
• Contact open → setpoint 1
• Contact closed → setpoint 2
• Input specification: 24 V - 15 mA
11 12 13 14 15 16
230 V
Alarm
4
5
6
10
11
C1
4
5
6
10
11
K
14 15 16
Pump relay No. 2
230 V - 8 A
Pump relay No. 1
230 V - 8 A
Shared
4
5
6
10
11
C2
Display for operation at full power (if P111 = max P)
Connector
1
2
J3 (CPU) 
Connect  the  signalling  of  the  unit  operating  at  max.  output  to 
terminals 1 and 2 of the connector on the CPU board.
• Output specification: 2 A under 250 V.
"Load shedding" function control
Connector
1
J6
J6 (CPU) 
(CPU)
Connector J2
1
J2
(Circuit board 2) ADD 2
(Carte circuit 2) ADD 2
Connect 1 to 4 contacts to the terminals of the connector of the 
CPU  board  according  to  the  number  of  the  compressors  to  be 
shed. 1 contact per compressor (contact free of any polarity and 
of good quality).
• Contact open → normal operation,
• Contact closed → compressor load shedding.
• Input specification: 24 V - 15 mA.
NOTE:
• Connection to be made on site by the customer,
• Precautions for connection. See manual for the regulator 
and the electrical diagram of the unit.
Communication
• In the room, a control and display console is used to run an 
instant check on the unit; it enables the user to communicate 
with the microprocessor, to configure the unit and to adjust 
the setpoints.
• Electronic remote control (option):
  Installed in the machine room, this will be connected to the 
unit by a pair of telephone-type wires (max. distance 1000 
m).  For  a  description  of  functions  and  connection,  see 
CHILLER/HEATPUMP CONTROL manual.
• Relay board(s) (option):
This board is installed in a cabinet in the machine room and 
can  remotely  report  on  all  the  unit's  operating  states  and 
faults by providing contacts which are potential-free when 
closed. The board will be connected to the unit by a pair of 
telephone-type wires (max. distance 1000 m).
• Communication with centralised management system and 
see the option in the CHILLER/HEATPUMP CONTROL
manual.
For  a  description  of  boards  and  connection,  see  the  CHILLER/ 
HEATPUMP CONTROL manual.
9 10 11
15 16
230 V
7
8
9
10
11
stage
N° 1 N° 2
7
8
9
stage
N° 3 N° 4
13