Self diagnosis function
We are constantly trying to do better service to our customers by installing such judges that show abnormality of each function as follows:
■
RUN light
1-time flash
2-time flash
5-time flash
TIMER light ON
6-time flash
TIMER light
1-time flash
2-time flash
RUN light
4-time flash
keeps flashing
RUN light
2-time flash
2 time flash
TIMER light
1-time flash
2-time flash
RUN light ON
3-time flash
4-time flash
5-time flash
6-time flash
7-time flash
Keep flashing
Fungsi diagnosis diri
Kita sentiasa berusaha untuk memberikan perkhidmatan yang lebih baik kepada pelanggan kita dengan memasang pengesan yang
■
menunjukkan kerosakan setiap fungsi seperti berikut:
Lampu RUN
Memancar 1 kali
Memancar 2 kali
Memancar 5 kali
Lampu TIMER ON
Memancar 6 kali
Lampu TIMER
Memancar 1 kali
Memancar 2 kali
Lampu RUN sentiasa
Memancar 4 kali
memancar
Lampu RUN
Memancar 2 kali
memancar 2 kali
Lampu TIMER
Memancar 1 kali
Memancar 2 kali
Lampu RUN ON
Memancar 3 kali
Memancar 4 kali
Memancar 5 kali
Memancar 6 kali
Memancar 7 kali
Terus berkedip
RLC012A006A_EIMV.indd 57
Description of trouble
Heat exchanger sensor error
Room temperature sensor error
Active filter voltage error
Indoor fan motor error
Description of trouble
Outdoor temperature sensor error
Outdoor heat exchanger fluid pipe
sensor error
Discharge pipe sensor error
Rotor lock
Description of trouble
Current cut
Trouble of outdoor unit
Over current
Power transistor error
Over heat of compressor
Error of signal transmission
Outdoor fan motor error
Cooling high pressure protection
Huraian masalah
Ralat sensor penukar haba
Ralat sensor suhu bilik
Ralat voltan penapis aktif
Ralat motor kipas dalam rumah
Huraian masalah
Ralat sensor suhu luar
Ralat sensor paip bendalir penukar
haba luar
Ralat sensor paip luahan
Rotor terkunci
Huraian masalah
Arus terputus
Masalah unit luar
Arus dilampaui
Ralat transistor kuasa
Pemampat terlalu panas
Ralat siaran isyarat
Ralat motor kipas luar
Perlindungan tekanan tinggi pendinginan
– 57 –
Cause
•
Broken heat exchanger sensor wire, poor connector connection
•
Broken room temperature sensor wire, poor connector connection
•
Defective power supply
•
Defective fan motor, poor connector connection
Cause
•
Broken outdoor sensor wire, poor connector connection
•
Broken heat exchanger fluid pipe sensor wire, poor connector connection
•
Broken discharge pipe sensor wire, poor connector connection.
•
Defective compressor
•
Open phase on compressor
•
Defective outdoor unit boards
Cause
•
Compressor locking, open phase on compressor output, shortcircuit on power
transistor, closed service valve
•
Broken power transistor, broken compressor wire
•
Broken discharge pipe sensor wire, poor connector connection
•
Compressor blockage
•
Overload operation, overcharge
•
Broken power transistor
•
Gas shortage, defective discharge pipe sensor, closed service valve
•
Defective power supply, Broken signal wire, defective in/outdoor unit boards
•
Defective fan motor, poor connector connection
•
Gas over charge, short circuit of outdoor unit
Sebab
•
Wayar sensor penukar haba terputus, sambungan penyambung kurang baik
•
Wayar sensor suhu bilik terputus, sambungan penyambung kurang baik
•
Bekalan kuasa lemah
•
Motor kipas rosak, sambungan penyambung kurang baik
Sebab
•
Wayar sensor luar terputus, sambungan penyambung kurang baik
•
Wayar sensor paip bendalir penukar haba terputus, sambungan penyambung
kurang baik
•
Wayar sensor paip luahan terputus, sambungan penyambung kurang baik.
•
Pemampat rosak
•
Pemampat dalam fasa terbuka
•
Papan unit luar rosak
Sebab
•
Pemampat terkunci, output pemampat dalam fasa terbuka, litar terpintas pada
transistor kuasa, injap perkhidmatan tertutup
•
Transistor kuasa rosak, wayar pemampat terputus
•
Wayar sensor paip luahan terputus, sambungan penyambung kurang baik
•
Pemampat tersumbat
•
Operasi beban lebih, cas berlebihan
•
Transistor kuasa rosak
•
Kekurangan gas, sensor paip luahan rosak, injap perkhidmatan tertutup
•
Bekalan kuasa lemah, Wayar isyarat terputus, papan unit dalam rumah/luar rosak
•
Motor kipas rosak, sambungan penyambung kurang baik
•
Kelebihan isi gas, hubung-singkat unit outdoor
29/11/2556 16:24:46