Self Diagnosis Function - Mitsubishi Heavy Industries SRK50ZMXA-S User Manual

Table of Contents

Advertisement

Self diagnosis function

We are constantly trying to do better service to our customers by installing such judges that show abnormality of each function as follows:
TIMER light ON
RUN light keeps flashing
RUN light ON
RUN light 2-time flash
RUN light 7-time flash
RUN light
Description of trouble
Heat exchanger sensor 1 error
1-time flash
2-time flash
Room temperature sensor error
3-time flash
Heat exchanger sensor 3 error
5-time flash
Active filter voltage error
6-time flash
Indoor fan motor error
Refrigerant is insufficient
7-time flash
Closed service valve
Heat exchanger sensor 1 error
TIMER light
Outdoor temperature sensor error
1-time flash
Outdoor heat exchanger fluid pipe
2-time flash
sensor error
Discharge pipe sensor error
4-time flash
Suction pipe sensor error
5-time flash
Current cut
1-time flash
Trouble of outdoor unit
2-time flash
Over current
3-time flash
Power transistor error
4-time flash
5-time flash
Over heat of compressor
Error of signal transmission
6-time flash
7-time flash
Outdoor fan motor error
Keep flashing
Cooling high pressure protection
Rotor lock
2-time flash
Closed service valve
1-time flash
– 29 –
Cause
• Broken heat exchanger sensor 1 wire, poor connector
connection
Broken room temperature sensor wire, poor connector
connection
• Broken heat exchanger sensor 3 wire, poor connector
connection
• Defective power supply
• Defective fan motor, poor connector connection
Refrigerant is insufficient, leaking
Closed serice valve
Broken heat exchanger sensor 1 wire, poor connector
connection
• Broken outdoor sensor wire, poor connector connection
Broken heat exchanger fluid pipe sensor wire, poor
connector connection
• Broken discharge pipe sensor wire, poor connector connection.
• Broken suction pipe sensor wire, poor connector connection
Compressor locking, open phase on compressor
output, shortcircuit on power transistor, closed service
valve
• Broken power transistor, broken compressor wire
• Broken discharge pipe sensor wire, poor connector connection
• Compressor blockage
• Overload operation, overcharge
• Broken power transistor
Gas shortage, defective discharge pipe sensor,
closed service valve
Defective power supply, Broken signal wire, defective
in/outdoor unit boards
• Defective fan motor, poor connector connection
• Gas over charge, short circuit of outdoor unit
• Defective compressor
• Open phase on compressor
• Defective outdoor unit boards
• Closed serice valve

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srk25zmxa-sSrk35zmxa-sSrk20zmxa-sSrk60zmxa-s

Table of Contents