Dc voltage input module (4 points, isolated, wide span voltage)

Advertisement

COMPONENT IDENTIFICATION
FRONT VIEW
RUN LED
ERR LED
■ STATUS INDICATOR LED
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with input circuit abnormality (AD con-
verter response failure);
Green in normal operating conditions.
PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R3CON for detailed operation.
■ CHANNEL INDIVIDUAL SETTING
PARAMETER
Zero Scale
Full Scale
Zero Adjust
Full Adjust
Unused
SIDE VIEW
1
11
2
12
3
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
AVAILABLE RANGE
-32000 to +32000
-32000 to +32000
-320.00 to +320.00
-32000 to +32000
0: Enable
1: Disable
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
SW3
4
3
2
Conv.
1
Rate
ON
■ SIDE DIP SW
(*) Factory setting
• Input Range: SW1, SW2
INPUT 1 (SW1)
INPUT 2 (SW1)
INPUT 3 (SW2)
INPUT 4 (SW2)
1
2
3
4
5
OFF OFF OFF OFF OFF OFF OFF OFF -30 – +30V (*)
ON
OFF OFF OFF ON
OFF ON
OFF OFF OFF ON
ON
ON
OFF OFF ON
• Conversion Rate: SW3-1, 3-2
CONVERSION RATE
SW
80 ms (*)
40 ms
SW3-1
OFF
ON
SW3-2
OFF
OFF
Note: Be sure to set unused SW3-3 and 3-4 to OFF.
DEFAULT SETTING
0
10000
0.00
1.0000
0: Enable
R3-SV4B
Functions
SW2
SW1
Range
8
8
Input 2 (SW1)
7
7
or
6
6
Input 4 (SW2)
5
5
4
4
Input 1 (SW1)
3
3
or
2
2
Input 3 (SW2)
1
1
ON
ON
RANGE
6
7
8
OFF OFF OFF -15 – +15V
OFF OFF 0 – 30V
ON
OFF OFF 0 – 15V
20 ms
10 ms
OFF
ON
ON
ON
EM-8415 Rev.5 P. 2 / 3