Managing Valve Purge - Honeywell TC300 Configuration And User's Manual

Commercial thermostat
Hide thumbs Also See for TC300:
Table of Contents

Advertisement

4 - CONFIGURATION
Operation Configuration
Hybrid
Control

Managing Valve purge

This setting for 2-pipe systems cycles valve to ensure accurate changeover
temperature sensor reading if there are infrequent heating or cooling cycles.
To configure Valve purge
1. Swipe left from the Home screen.
2. On the Quick access screen, tap
The Valve Purge screen appears.
3. Set the purge time and interval.
76
Table 26: Pipe sensor threshold (Continued)
Range
Type
Temp Offset (Heat) 5 to 10°F (Default
5°F)
Timeout Timer
1 to 4 hours (Default 4
(Heat)
hours)
Temp Offset (Cool)
-10 to -5°F (Default
-5°F)
Timeout Timer
1 to 4 hours (Default 4
(Cool)
hours)
Figure 55 Valve purge
Description
When the pipe temperature is above the
space temperature and the hybrid control is
enabled, than the offset is suitable for
heating.
When the configured timer expires, the pipe
sensor reading is compared to the threshold
setting, if the pipe sensor reading is above
the threshold, it will generate water
temperature. No heating alarm will be
raised.
When the pipe temperature is below the
space temperature and the hybrid control is
enabled, than the offset is suitable for
cooling.
When the configured timer expires, the pipe
sensor reading is compared to the threshold
setting, if the pipe sensor reading is below
the threshold, it will generate water
temperature. No cooling alarm will be raised.
> Advanced > Valve Purge.
Managing Valve purge