4 - CONFIGURATION
If Output is set to 2-10 Vdc
- Heating Rage: 2.0-5.7 Vdc
- Cooling Range: 6.3-10.0 Vdc
- Off voltage is 6.0 Vdc
2-Pipe Single Coil
3. Tap 2-Pipe Single Coil.
The 2-Pipe Single Coil screen appears.
Heating/Cooling type
Changeover
Heat & Cool
Heat only
54
Table 21: 2-Pipe single coil
Controls
Options
Pipe sensor
Network Input
Changeover
Switch
On/Off
Normally closed
Normally open
Floating
Modulating
Control
Setting
On/Off
Normally closed
Normally open
Floating
Modulating
Control
Setting
Description
Set the pipe sensor as input value for
changeover method.
Set the network input as input value for
changeover method.
Set the digital input as input value for
changeover method.
•
Set Valve output type as N.C
•
Set Valve output type as N.O
•
Set output type Direct or Reverse
•
Set Valve run time
•
Set Min position when enabled
•
Enable sync at mid night
•
Set min output when enabled
•
Use Stage 1 as enable
•
Set output type Direct or Reverse
•
Set Min output of Modulating
valve
•
Set Max output of Modulating
valve
•
Set Valve output type as N.C
•
Set Valve output type as N.O
•
Set output type Direct or Reverse
•
Set Valve run time
•
Set Min position when enabled
•
Enable sync at mid night
•
Set min output when enabled
•
Use Stage 1 heat as enable
•
Set output type Direct or Reverse
•
Set Min output of Modulating
valve
•
Set Max output of Modulating
valve
Equipment configuration