Honeywell TC300 Configuration And User's Manual page 71

Commercial thermostat
Hide thumbs Also See for TC300:
Table of Contents

Advertisement

Operation Configuration
Stops
Limits
Managing Setpoint options
Figure 51 Setpoint options
Table 23: Setpoint options
Range
Type
Cooling Min.
50-99°F (Default
Setpoint
50°F)
Heating Max.
40-105°F (Default
Setpoint
90°F)
Thermostat
2°F-8°F(Default: 3°F) Ensures that the heat setpoint and the cool
Deadband
Temporary Setpoint
0°F - 45°F (Default
Limit
30°F)
MANAGING SETPOINT OPTIONS
Description
The minimum cool setpoint that can be set
by the user
The maximum heat setpoint can be set by
the user
setpoint maintain a differential minimum
temperature span the thermostat is in auto
mode.
The range above or below occupied setpoint
by which the temperature may be altered by
user from programmed scheduled setpoint
in occupied state or when initiating
temporary override of schedule. This
includes scheduled occupancy or override
of the scheduled occupancy (bypass
override). During unoccupied and standby
periods, the effective setpoint offset is set to
Δ
0
°F. If an occupant wants to change the
temporary setpoint, the occupant must first
override the schedule to occupied and then
the thermostat will allow the occupant to
change the temporary setpoint
71