Occupancy setpoints

Name
Cfg_Setpoints_OccHeatSp
Cfg_Setpoints_OccCoolSp
Cfg_Setpoints_StbyHeatSp
Cfg_Setpoints_StbyCoolSp
Cfg_Setpoints_UnOccHeatSp
Cfg_Setpoints_UnOccCoolSp

Purge

Name
Cfg_PipePurgeTime
Cfg_PipePurgeInterval
Cfg_ValveCycle
Cfg_TimeOut
Cfg_HybridControlEna
bleHeat
Cfg_HybridControLEn
ableCool
62
Table 26 Occupancy setpoints
BACnet
Object Type
Analog Value
Analog Value
Analog Value
Analog Value
Analog Value
Analog Value
BACnet
BACnet
Object
Object
Type
Instance
Analog
2025
Value
Analog
2079
Value
Multistate
2025
Value
Analog
2080
Value
Binary
2053
Value
Binary
2054
Value
BACnet
Default
Object
Value
Instance
7
68 °F
4
76 °F
8
65 °F
5
80 °F
9
55 °F
6
85 °F
Table 27 Purge
Default
Range
Value
5
0 to 5 minutes
minutes
0.5 hours
0.5 to 2 hours
1
enum{
1min/24hours=1,
2min/24hours=2,
Disable=3}
4 hours
1 to 4 hours
1
Off=0,
On=1
1
Off=0,
On=1
Range
Description
40 to 99 °F
Occupied
heating
setpoint
40 to 99 °F
Occupied
cooling
setpoint
40 to 99 °F
Standby
heating
setpoint
40 to 99 °F
Standby
cooling
setpoint
40 to 99 °F
Unoccupied
heating
setpoint
40 to 99 °F
Unoccupied
cooling
setpoint
Description
Pipe purge duration
Pipe purge interval
Valve cycle type
When heating keeps working for
timeout time check whether pipe
temperature meet pipe sensor
threshold.
2 pipe single coil heat hybrid
control enable flag
2 pipe single coil cool hybrid
control enable flag
Occupancy setpoints