Parameters With Optional Alignment - DAB PUMPS MCE-22/P Instruction For Installation And Maintenance

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 65
FI
Flow sensor
FK
K factor
FD
Pipe diameter
FZ
Zero flow frequency
FT
Min. flow threshold
MP
Minimum pressure pump stop due to water failure
ET
Exchange time
AC
Acceleration
NA
Number of active inverters
NC
Number of simultaneous inverters
CF
Carrier frequency
TB
Dry run time
T1
Shutdown time after low pressure signal
T2
Shutdown time
GI
Integral gain
GP
Proportional gain
FL
Minimum Frequency
I1
Input 1 setting
I2
Input 2 setting
I3
Input 3 setting
I4
Input 4 setting
OD
Type of system
PR
Pressure sensor
PW
Password Settings
4.3.1.2.1
Automatic alignment of sensitive parameters
When a multi inverter system is detected, the unit checks for consistency of the set parameters. If the sensitive parameters are not
aligned on all inverters, the display of each inverter shows a message requesting whether to transfer the configuration of the specific
inverter to the entire system. On acceptance, the sensitive parameters on the inverter where confirmation is given are distributed to all
other inverters in the series.
If there are configurations incompatible with the system, the configuration cannot be aligned from these inverters.
During normal operation, modification of a sensitive parameter on an inverter will cause automatic alignment of the parameter on all
other inverters without any request for confirmation.
Automatic alignment of sensitive parameters has no effect on all other types of parameter
In the particular case of inserting an inverter with default settings in the series (in the case of an inverter which replaces an existing
model or an inverter with restored factory settings), if the configurations applied, with the exception of factory settings, are consistent,
the inverter with the factory settings will automatically take on the sensitive parameters of the series.
4.3.1.3

Parameters with optional alignment

These are the parameters that are admissible even if not aligned with other inverters. Each time these parameters are modified, when
SET or MODE is pressed, the request is displayed whether to modify the entire communicating inverter series. In this way if the series
has all the same settings, the same data does not need to be set on all inverters.
List of parameters with optional alignment:
 LA
Language
 RC
Rated current
 MS Measurement system
 FS
Maximum frequency
 SO
Min. dry-running factor threshold
 AE
Anti-blocking
 O1
Output 1 function
 O2
Output 2 function
ENGLISH
93
.