DAB PUMPS MCE-22/P Instruction For Installation And Maintenance page 86

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 65
With reference to the example in Figure 10 and using the factory settings of the inputs (I1 = 1; I2 = 3; I3 = 5; I4=10) the following is
obtained:
When the switch is closed on I1 the pump blocks and error code "F1" is displayed
(e.g. I1 connected to a float; see para. 6.6.13.2 External float function settings).
When the switch is closed on I2 the control pressure becomes "P2"
(see para. 6.6.13.3 Auxiliary pressure input function settings).
When the switch is closed on I3 the pump blocks and error code "F3" is displayed
(see para. 6.6.13.4 Settings for system enable and fault reset).
When the switch is closed on I4 after time T1 the pump blocks and error code F4 is displayed.(see para. 6.6.13.5 Setting
low pressure detection).
The example in Figure 10, refers to a connection with voltage-free contact, using the internal voltage to control the inputs (obviously
using only useful inputs).
If a voltage rather than a contact is available, this can still be used to control the inputs: in this case terminals +V and GND are not
used and the voltage source (complying with the specifications of Table 7) is connected to the required input. If an external voltage is
used to control the inputs, all the circuitry must be protected by double insulation
CAUTION: the pairs of inputs I1/I2 and I3/I4 have a pole in common for each pair.
ENGLISH
.
83

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mce-15/pMce-11/pMce-55/pMce-30/pMce-150/pMce-110/p

Table of Contents