Hitachi RER670 Commissioning Manual page 151

Railway application
Hide thumbs Also See for RER670:
Table of Contents

Advertisement

1MRK 506 377-UEN Rev. L
Document
revision
E
F
G
H
J
K
10.12.6.2
Verifying signals and settings
The fault locator (RWRFLO) relies on information from two other functions:
Phase selection information provided by the distance protection function
Analog information provided by the trip value recorder function
Check that binary start and phase selection signals are connected, and that voltage and current
signals are configured (parameter settings).
The result is displayed on the local HMI or via PCM600. Distance-to-faults for the last 1000 recorded
disturbances can be found on the local HMI under Main menu/Disturbance records /Disturbance
#n (n = 1-100)/General Information.
In PCM600, including loop selection information the result is displayed on the recording list after
upload.
The function can be selected for 2Phase or ATCatenary using the setting SystemType. Sequence of
voltage and current to be applied for verifying signals and settings.
Railway application RER670
Commissioning manual
Product
History
revision
2.2.3
-
2.2.4
-
2.2.4
-
2.2.4
-
2.2.4
-
2.2.5
BCD outputs are provided and BTCatenary SystemType included. This update is valid for
2.2.5 release only.
© 2017 - 2022 Hitachi Energy. All rights reserved
Section 10
Testing functionality by secondary injection
GUID-D928E80E-F2DD-4704-9C6C-5AB4302A7D33 v2