12. OUTDOOR INSTALLATION
12-2. Spacing
External dimension.
MXZ-SM36/48/60NAM2
MXZ-SM36/42/48NAMHZ2
12-2-1. Spacing individual
Follow Fig. 12-2-2~7 to space individual at the installation site.
Fig. 12-2-2
Obstacles at rear only
Fig. 12-2-4
Obstacles at rear and sides only
* Using an optional air outlet guide, the
clearance >= 500 mm [19-11/16"].
Fig. 12-2-6
Obstacles at front and rear only
M-P0890
mm[in.]
Fig. 12-2-1
mm[in.]
Fig. 12-2-3
Obstacles at rear and above only
* Using an optional air outlet guide, the
clearance >= 500 mm [19-11/16"].
Fig. 12-2-5
Obstacles at front only
1500
[59-1/16"]
500
[19-11/16"]
* NO upward airflow outlet guide.
Fig. 12-2-7
Obstacles at rear, sides and above only
12-2-2. Spacing grouped
Follow Fig. 12-2-8~13 to space grouped at the installation site.
Leave 10 mm [13/32"] space or more between units.
* When using an optional air outlet guide,
the clearance is 1000 mm [39-3/8"] or more.
Fig. 12-2-8
Obstacles at rear or front only
* Using an optional air outlet guide, the
clearance >= 1000 mm [39-3/8"].
Fig. 12-2-10
Obstacles at front and rear only
* Using an optional air outlet guide for upward
airflow, the clearance >= 1500 mm [59-1/16"].
Fig. 12-2-12
Parallel groups arrangement
SMART MULTI
mm[in.]
* In case of side-by-side installation,
<=3 units;
* Do not install the optional air outlet guides
for upward airflow.
Fig. 12-2-9
Obstacles at rear and above only
* Using an optional air outlet guide, the
clearance >= 1000 mm [39-3/8"].
Fig. 12-2-11
Parallel individuals arrangement
* Stacked layer <= 2 units;
* Side-by-side stacked groups <= 2 groups;
Fig. 12-2-13
Stacked groups arrangement
81