12. OUTDOOR INSTALLATION
MXZ-SM72/96/120TAM-U1
Fig. 12-2-14
12-2-3. Spacing individual MXZ-SM72/96/120TAM-U1
Follow Fig. 12-2-15~20 to space individual
MXZ-SM72/96/120TAM-U1 at the installation site.
Fig. 12-2-15
Obstacles at rear only
Fig. 12-2-17
Obstacles at rear and sides only
* Using an optional air outlet guide, the
clearance >= 500 mm [19-11/16"].
Fig. 12-2-19
Obstacles at front and rear only
M-P0890
mm[in.]
mm[in.]
Fig. 12-2-16
Obstacles at rear and above only
* Using an optional air outlet guide, the
clearance >= 500 mm [19-11/16"].
Fig. 12-2-18
Obstacles at front only
* NO upward airflow outlet guide.
Fig. 12-2-20
Obstacles at rear, sides and above only
12-2-4. Spacing grouped MXZ-SM72/96/120TAM-U1
Follow Fig. 12-2-21~26 to space grouped MXZ-SM72/96/120
TAM-U1 at the installation site. Leave 25 mm space or space or
more between MXZ-SM72/96/120TAM-U1 units.
* When using an optional air outlet guide,
the clearance is 1000 mm [39-3/8"] or more.
Fig. 12-2-21
Obstacles at rear or front only
* Using an optional air outlet guide, the
clearance >= 1000 mm [39-3/8"].
Fig. 12-2-23
Obstacles at front and rear only
* Using an optional air outlet guide for upward
airflow, the clearance >= 1500 mm [59-1/16"].
Fig. 12-2-25
Parallel groups arrangement
SMART MULTI
mm[in.]
* In case of side-by-side installation, <=3 units;
* Do not install the optional air outlet guides
for upward airflow.
Fig. 12-2-22
Obstacles at rear and above only
* Using an optional air outlet guide, the
clearance >= 1000 mm [39-3/8"].
Fig. 12-2-24
Parallel individuals arrangement
* Stacked layer <= 2 units;
* Side-by-side stacked groups <= 2 groups;
Fig. 12-2-26
Stacked groups arrangement