S+S Regeltechnik RCO2 Operating And Mounting Instructions Manual page 37

Multifunctional room sensor and measuring transducer for humidity, temperature, air quality (voc), fine dust (pm) and co2 content, calibratable, with modbus connection
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 16
F
AERASGARD
®
RFTM - LQ - PS - CO2 - Modbus | Télégrammes
TÉLÉGRAMMES
Function 04 Read Input Register
Registre
Paramètre
3x0001
CO2
3x0002
CO2
3x0003
COV [%]
3x0004
COV [%]
3x0005
Température
3x0006
Température
3x0007
Humidité relative
3x0008
Humidité relative
3x0009 * non affecté
3x0010 *
non affecté
3x0011 *
Position du potentiomètre
3x0012
COV [ppb]
3x0013
COV [ppb]
3x0014
Particules fines (PM)
3x0015
Particules fines (PM)
* uniquement pour version d'appareil avec potentiomètre de consigne
Function 05 Write Single Coil
Registre
Paramètre
0x0001
Réinitialisation (Autozero) CO2
0x0002
Réinitialisation (Autozero) COV
0x0003
Calibrage automatique (Automatic) CO2
0x0004
non affecté
0x0005
Sensibilité COV "low"
0x0006
Sensibilité COV "medium"
0x0007
Sensibilité COV "high"
0x0008
Rétroéclairage LCD
Système d'unités
0x0009
Température
0x0010
Particules fines (PM) taille de particule
Balayage 4 s
Signed 16 Bit
Filtrage 32 s
Signed 16 Bit
Balayage 4 s
Signed 16 Bit
Filtrage 32 s
Signed 16 Bit
Balayage 4 s
Signed 16 Bit
Filtrage 32 s
Signed 16 Bit
Balayage 4 s
Signed 16 Bit
Filtrage 32 s
Signed 16 Bit
aucun filtrage
Signed 16 Bit
Balayage 4 s
Unsigned 16 Bit
Filtrage 32 s
Unsigned 16 Bit
Balayage 4 s
Signed 16 Bit
Filtrage 32 s
Signed 16 Bit
SI
→ Impérial
[°C]
→ [°F]
37
Data Type
Value
350...5000
350...5000
0...1000
0...1000
0...500
320...1220
0...500
320...1220
0...1000
0...1000
0...1000
0...60 000
0...60 000
0...1000
0...1000
Data Type
Value
Bit 0
0 / 1
Bit 1
0 / 1
Bit 2
0 / 1
Bit 4
0 / 1
Bit 5
0 / 1
Bit 6
0 / 1
Bit 7
0 / 1
Bit 8
0 / 1
Bit 9
0 / 1
Range
350...5000 ppm
350...5000 ppm
0.0...100.0 % VOC
0.0...100.0 % VOC
0.0... +50.0 °C
+32.0...+122.0 °F
0.0... +50.0 °C
+32.0...+122.0 °F
0.0...100.0 % RH
0.0...100.0 % RH
0.0...100.0 %
0...60 000 ppb
0...60 000 ppb
0...1000 µg/m
3
0...1000 µg/m
3
Range
OFF - ON
OFF - ON
OFF - ON
OFF - ON
OFF - ON
OFF - ON
OFF - ON
SI (Default) -
Impérial
PM 2,5 / PM 10