Electrical connection

4.1

General recommendations

The compressor terminal box has a wiring diagram on the inside of its cover. Before connecting the
compressor, ensure the supply voltage, the phases and the frequency match the nameplate data.
For safety reasons, Emerson recommends that the electrical installation be executed in compliance
with standard EN 60204-1 and/or other standards and regulations of application.
When installing YBD*K1E compressors in a system, the following measures must be taken:
▪ To ensure the wires are properly terminated, the correct terminal and clamping tool for the
selected wire size must be used.
▪ The ground wiring must conform to local regulations and codes of practice (only the provided
parts must be used).
▪ The grounding screw must be torqued to 2.4 to 2.6 Nm.
▪ A cable strain-relief device must be added.
▪ Cable and wires must be protected against sharp edges.
4.2

Electrical installation

WARNING
Conductor cables! Electrical shock hazard! Shut off power supply before
undertaking any task on electrical equipment.
WARNING
Ignition source in a potentially flammable atmosphere! Fire hazard! In
applications with A2L refrigerants, the electrical connection of the scroll
compressors is not an ignition source during normal operation but could
become one if not installed properly according to installation instructions.
Ensure correct mechanical and electrical installation.
System capacitors may remain charged for several minutes after shutdown.
Before starting to work on the electrical installation make sure sparking is not
possible. Continuously check if the ambient atmosphere is non-flammable
when working on the electrical installation.
For recommended wiring diagrams, see Figure 19 next page.
NOTE: A contactor K2 has to be used for the safety chain to comply with EN 60335 and
EN 60204-1.
NOTE: A residual current device (RCD) can be used for additional protection in applications
using A2L refrigerants such as R454C, R455A, R454A and R1234yf. The purpose of the RCD
is to detect current leaks to the ground in case of electrical issues, for example with the
terminal connection pins or other electrical accessories.
Figure 18: Residual current device (RCD)
20
AGL_Ref_DG_YBDK1E_EN_Rev04