ACCESSORY LIST
FUSE ELEMENT
FUSE ELEMENT

INSTALLATION

a) Capacity of equipment
INPUT VOLTAGE
FREQUENCY & PHASE
MAXIMUM RATING OF EQUIPMENT
CAPACITY OF FUSE (B CLASS)
INPUT CABLE
OUTPUT CABLE
− Provide a Switch Box for every Welding Power Source, and use designated fuse
− Tolerance of Power Voltage Variation is ± 10% of rated input voltage.
− 100 Amps MCB to be used as alternative to SFU.
b) Installation place
− Install in the place where less moisture and dust exist. Avoid direct sunlight and
rain, and maintain ambient temperature within –10
− Keep the welding power source at least 20 cm. away from the wall (if any).
− In case of installation of more two units side by side, a distance of more than 20
cm is recommended between the two power sources.
− Use a shield to protect the welding arc in case of excessive air draft.
3A
1A
EASY WELD
SSR-400
21.6 KVA
32 Amps HRC
2
8mm
or more
50mm
Minimum
4
1 Piece
1 Piece
EASY WELD
SSR-600
415 V ± 10% AC
50 Hz, 3 PHASE
40 KVA
60 Amps HRC
2
22m
or more
2
(Cu)
70mm
Minimum
o
o
to 45
C as much as possible.
2
(Cu)