Daikin HUBBARD HCU2040PXB1 Installation, Commissioning And Maintenance Manual page 110

Hermetic r744 condensing units
Table of Contents

Advertisement

Mask index
Display description
Caf04
Refrigerant type
Caf05
Min.time on
Min.time off
Minimum time to start same
comp.
Caf06
Startup
Caf07
Star time
Star delay/line
Star delta delay
Caf08
Partwinding delay
Caf09
Equalization
Equal. time
Caf10
Device rotation type
Caf11
Device sequence
Caf12
Load up time
Shutdown time
Unloader delay
Caf13
Custom rotation on order
Caf14
Custom rotation off
Caf15
Modulation device
Caf16
Min frequency
Max frequency
Caf17
Min.time on
Min.time off
Minimum time to start same
comp.
Caf18
Digital comp. valve
regulation
Cycle time
Caf19
Oil dilution
Discharge temp
...
...
Caf90
Diff erent sizes
Diff erent number of valves
Caf91
S1
...
S4
Caf92
S1
...
S4
Caf93
C01
...
C12
Caf95
Min.time on
Min.time off
Minimum time to start
same comp.
Reactivate startup procedure
after
Cag01
Minimum voltage
Maximum voltage
Nominal freq.
Nominal power
Cag02
Rising time
Falling time
Cag03
Enable compressor modulat.
in dead zone
Cag04
Enable suction press.backup
probe
Cag05
Request in case of regulation
probe fault
Pumpdown
Threshold
Cag06
Enable anti return of liquid
Delay
Copyright HPL March 2021
Description
Type of refrigerant (suction line 1)
Minimum compressor on time (line 1)
Minimum compressor off time (line 1)
Minimum time between starts of same compressor (line 1)
Type of compressor startup
Star relay run time
Delaty betwen star and line relay
Delay between star and delta relay
Partwinding delay
Enable compressor equalization at startup
Equalization duration
Type of rotation
Unloader sequence in relation to compressor activation (C=compressor, P=unloader)
Delay between diff erent compressor starts
Delay between diff erent compressor shutdowns
Delay between stages
Order of startup for compressor custom rotation
Order of shutdown for compressor custom rotation
Compressor modulating device type (line 1)
Minimum inverter frequency
Maximum inverter frequency
Minimum time compressor controlled by inverter on (line 1)
Minimum time compressor controlled by inverter off (line 1)
Minimum time compressor controlled by inverter startup (line 1)
Digital Scroll™ compressor valve control type (line 1)
Cycle time (line 1)
Enable Digital Scroll™ oil temperature alarm (line 1)
Enable Digital Scroll™ discharge temperature alarm (line 1)
...
Enable compressors of diff erent sizes (line 1)
Enable compressor partialization (line 1)
Enable size and size for compressor group 1 (line 1)
...
Enable size and size for compressor group 4 (line 1)
Enable stages and stages for compressor group 1 (line 1)
...
Enable stages and stages for compressor group 4 (line 1)
Size group for compressor 1 (line 1) or presence of inverter (line 1)
...
Size group for compressor 6 (line 1)
Minimum time on for Digital Scroll
TM
compressor (line 1)
Minimum time off for Digital Scroll
TM
compressor (line 1)
Minimum time between startups for Digital Scroll
Time for reactivation of startup procedure for Digital Scroll
Voltage corresponding to the minimum capacity of the inverter (line 1)
Voltage corresponding to the maximum capacity of the inverter (line 1)
Nominal frequency (frequency at nominal capacity) (line 1)
Nominal capacity for compressor managed by inverter at nominal frequency (line 1)
Time to pass from minimum to maximum capacity for modulating device (line 1)
Time to pass from maximum to minimum capacity for modulating device (line 1)
Enable compressor 1 modulation inside dead zone (line 1)
Enable screens for the confi guration of the suction pressure backup probe (line 1)
Compressor forcing value in case of suction probe fault (line 1)
Enable pumpdown function (line 1)
Pumpdown end threshold (line 1)
Enable liquid non return function (line 1)
Delay liquid non return function (line 1)
TM
compressor (line 1)
TM
compressor (line 1)
61
Page 110 of 169
Def.
U. of M.
Values
R744
---
R22
| R134a
R404A | R407C
R410A | R507A
R290 | R600
R600a | R717
R744 | R728
R1270 | R417A
R422D | R413A
R422A | R423A
R407A | R427A
R245Fa | R407F | R32
30
s
0...999
120
s
0...999
360
s
0...999
direct
---
Direct
Part winding
Star delta
0
ms
0...9999
0
ms
0...9999
0
ms
0...9999
0
ms
0...9999
NO
---
NO | YES
0
s
0...999
FIFO
---
---
FIFO
LIFO
TIME
CUSTOM
CpppCppp ---
----
CCpppppp
CpppCppp
10
s
0...999
0
s
0...999
0
s
0...999
1
---
1...16
1
---
1...16
None
---
None
Inverter
Digital scroll
30
Hz
0...150
60
Hz
0...150
30
s
0...999
60
s
0...999
180
s
0...999
Optimized
---
Optimized regulat.
regulation
Variable cycle time
Fixed cycle time
13
s
12...20
enable
---
disable | enable
enable
---
disable | enable
...
...
...
NO
---
NO | YES
NO
---
NO | YES
YES'
---
NO | YES
10.0
kW
0.0...500.0
...
...
...
NO
---
---
---
NO | YES
kW
0.0...500.0
YES'
---
NO | YES
100
%
100 | 50 | 100 | 50
75 | 100 | 25 | 50
75 | 100 | 33 | 66|100
...
...
...
NO
---
NO | YES
---
kW
S1...S4
S1
---
S1...S4 | INV
...
...
...
S1
---
S1...S4
60
s
0...999
180
s
0...999
360
s
0...999
480
min
0...9999
0.0
V
0.0...10.0
10.0
V
0.0...10.0
50
Hz
0...150
10.0
kW
0.0...500.0
90
s
0...600
30
s
0...600
AB
---
Disabled
abled
NO
---
NO | YES
50.0
%
0.0...100.0
Disabled
---
disabled
abled
1.5 barg
...
... (**)
NO
---
NO | YES
0
min
0...15
P4367 Rev 01
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017