Omron 3G3JV-A2015 User Manual page 115

Hide thumbs Also See for 3G3JV-A2015:
Table of Contents

Advertisement

Maintenance Operations
Fault
Fault name and meaning
display
uU1
Main circuit undervoltage
(UV1)
The main circuit DC voltage
has reached the undervoltage
detection level (230 V DC for
the 3G3JV-A2j-A, 160 V DC
for the 3G3JV-ABj-A, and
460 V DC for the
3G3JV-A4j-A).
%h
Radiation fin overheated
(OH)
The temperature of the
radiation fins of the Inverter
has reached 110_C ± 10_C.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Probable cause and remedy
• Power supply to the Inverter has phase loss, power input
terminal screws are loose, or the power cable is discon-
nected.
→ Check the above and take necessary countermeasures.
• Incorrect power supply voltage
→ Make sure that the power supply voltage is within
specifications.
• Momentary power interruption has occurred.
→ Use the momentary power interruption compensation
(Set n47 so that the Inverter restarts after power is
restored)
→ Improve the power supply.
• The internal circuitry of the Inverter is damaged.
→ Change the Inverter.
• The ambient temperature is too high.
→ Ventilate the Inverter or install a cooling unit.
• The load is excessive.
→ Reduce the load.
→ Decrease the Inverter capacity.
• The V/f setting is incorrect.
→ Reduce the V/f set voltage.
• The acceleration/deceleration time is too short.
→ Increase the acceleration/deceleration time.
• The ventilation is obstructed.
→ Change the location of the Inverter to meet the
installation conditions.
• The cooling fan of the Inverter does not work.
→ Replace the cooling fan.
Chapter 7
7-3

Advertisement

Table of Contents
loading

Table of Contents