(2) Method for Obtaining the Equivalent Piping Length
Equivalent length = (length of piping to farthest indoor unit) + (0.3 o number of bends in the piping) (m)
4-5-1. Correction of Heating Capacity for Frost and Defrosting
If heating capacity has been reduced due to frost formation or defrosting, multiply the capacity by the appropriate correction
factor from the following table to obtain the actual heating capacity.
Correction factor diagram
Outdoor Intake temperature <W.B.°F (°C)>
Correction factor
OCH695B
20
40
60
80
100
43(6)
37(4)
36(2)
32(0) 28(−2) 25(−4) 21(−6) 18(−8) 14(−10) 5(−15) −4(−20) −13(−25)
1.0
0.98
0.89
0.88
Total capacity of indoor unit
120
140
160
180
Piping equivalent length (ft)
0.89
0.9
0.95
30
200
220
240
260
0.95
0.95
0.95
0.95
0.95