Mitsubishi Electric PUMY-P36NKMU2-BS Technical & Service Manual page 15

Table of Contents

Advertisement

<Heating>
Outdoor Design Wet Bulb Temperature
Total Heating Load
Room1
Indoor Design Dry Bulb Temperature
Heating Load
Room2
Indoor Design Dry Bulb Temperature
Heating Load
<Other>
Indoor/Outdoor Equivalent Piping Length
Capacity of indoor unit
Model Number
Model 05
Model 06
for indoor unit
Model
5.6
Capacity
2. Heating Calculation
(1) Temporary Selection of Indoor Units
Room1
PEFY-P15
Room2
PEFY-P18
(2) Total Indoor Units Capacity
P15 + P18 = P33
(3) Selection of Outdoor Unit
The P36 outdoor unit is selected as total indoor units capacity is P33
PUMY-P36
(4) Total Indoor Units Capacity Correction Calculation
Room1
Indoor Design Dry Bulb Temperature Correction (69.8ºF)
Room2
Indoor Design Dry Bulb Temperature Correction (73.4ºF)
Total Indoor Units Capacity (CTi)
CTi = Σ (Indoor Unit Rating × Indoor Design Temperature Correction)
= 17.0 × 1.00 + 20.0 × 0.92
= 35.4 kBtu/h
(5) Outdoor Unit Correction Calculation
Outdoor Design Wet Bulb Temperature Correction (35.6ºF)
Piping Length Correction (328 ft)
Defrost Correction
Total Outdoor Unit Capacity (CTo)
CTo = Outdoor Unit Rating × G(CTi)
× Piping Length Correction × Defrost Correction
= 42.0 × 1.0 × 0.94 × 0.89
= 35.1 kBtu/h
*1 G(CTi) is used only when greater than 100% indoor model size are connected in total,
refer to STANDARD CAPACITY DIAGRAM.
Table 1 Table of correction factor at frost and defrost
Outdoor Intake temperature <W.B.°F (°C)>
Correction factor
(6) Determination of Maximum System Capacity
Comparison of Capacity between Total Indoor Units Capacity (CTi) and Total Outdoor Unit Capacity (CTo)
CTi = 35.4 > CTo = 35.1, thus, select CTo.
CTx = CTo = 35.1 kBtu/h
(7) Comparison with Essential Load
Against the essential load 34.4 kBtu/h, the maximum system capacity is 35.1 kBtu/h: Proper outdoor units have been selected.
(8) Calculation of Maximum Indoor Unit Capacity of Each Room
CTx = CTo, thus, calculate by the calculation below
Room1
Maximum Capacity × Room1 Capacity after the Temperature Correction/(Room1,2 Total Capacity after the Temperature Correction
= 35.1 × (17.0 × 1.00) / (17.0 × 1.00 + 20.0 × 0.92)
= 16.9 kBtu/h
Room2
Maximum Capacity × Room1 Capacity after the Temperature Correction/(Room1,2 Total Capacity after the Temperature Correction
= 35.1 × (20.0 × 0.92) / (17.0 × 1.00 + 20.0 × 0.92)
= 18.2 kBtu/h
Completed selecting units since the selected units fulfill the heating loads of Room 1, 2.
OCH695B
Design Condition
Model 08
Model 12
Model 15
6.7
9.0
13.5
17.0 kBtu/h (Rated)
20.0 kBtu/h (Rated)
42.0 kBtu/h
*1
× Outdoor Design Temperature Correction
43(6)
37(4)
36(2)
32(0)
1.0
0.98
0.89
0.88
OK: fulfills the load 16.3 kBtu/h
OK: fulfills the load 18.1 kBtu/h
35.6ºF (2.0ºC)
34.4 kBtu/h
69.8ºF (21.0ºC)
16.3 kBtu/h
73.4ºF (23.0ºC)
18.1 kBtu/h
328 ft
Model 18
Model 24
Model 27
17.0
20.0
27.0
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
Figure 4 Indoor unit temperature correction
1.00 (Refer to Figure 4)
0.92 (Refer to Figure 4)
Figure 5 Outdoor unit temperature correction
1.00
1.0 (Refer to Figure 5)
0.94 (Refer to Figure 6)
0.95
0.89 (Refer to Table 1)
0.90
0.85
0.80
0.75
0.70
Figure 6 Correction of refrigerant piping length
28(−2)
25(−4)
21(−6)
18(−8)
0.89
0.9
0.95
0.95
15
Model 30
Model 36
Model 48
30.0
34.0
40.0
59
60.8 62.6 64.4 66.2
68
69.8 71.6 73.4 75.2
77
15
16
17
18
19
20
21
22
23
24
25
Indoor Temperature
To be used to correct indoor unit only
1.4
1.3
1.2
1.1
21.1°C (70.0°F) D.B.
1.0
0.9
0.8
0.7
0.6
0.5
0.4
-13
-4
5
14
23
32
41
-25
-20
-15
-10
-5
0
5
Outdoor Temperature
To be used to correct outdoor unit only
Total capacity of indoor unit
0
50
100
150
200
250
300
350
400
450
Piping equivalent length (ft)
14(−10)
5(−15)
−4(−20) −13(−25)
0.95
0.95
0.95
0.95
(kBtu/h)
Model 54
54.0
60.0
[°F D.B.]
78.8 80.6
26
27
[°C D.B.]
Indoor
Temperature
50
59
[°F W.B.]
10
15
[°C W.B.]
500
550
600

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents