OPERATING PROCEDURE
13. Removing the compressor (MC)
(1) Remove the service panel. (See Figure 1)
(2) Remove the top panel. (See Figure 1)
(3) Remove 2 front cover panel fixing screws (5 × 12) and
remove the front cover panel. (See Photo 3)
(4) Remove front panel fixing screws, 5 (5x12) and 2 (4 x
10) and remove the front panel. (See Photo 3)
(5) Remove 4 back cover panel fixing screws (5 × 12) and
remove the back cover panel.
(6) Remove the electrical parts box. (See Photo 4)
(7) Remove the valve bed. (Refer to procedure 8 (4))
(8) Remove the right side panel. (Refer to procedure 8 (7))
(9) Remove 3 separator fixing screws (4 × 10) and remove
the separator. (See Figure 2)
(10) Recover refrigerant.
(11) Remove the 3 compressor fixing nuts for motor using
spanner or adjustable wrench.
(12) Remove the welded pipe of motor for compressor inlet
and outlet and then remove the compressor.
Note: Recover refrigerant without spreading it in the
air.
OCH695B
PHOTOS/FIGURES
Photo 12
Valve bed
Valve bed
fixing screw
Compressor
(MC)
Separator
Figure 2
Separator
fixing screw
140
Valve bed
fixing screws
Accumulator
Compressor
fixing nuts
Separator
fixing
screws

Hide quick links: