4 EN – Quick installation guide
Select the power cables
Size the power cables according to local regulations to carry the nominal current
given on the type designation label of your drive.
Typical power cable sizes are listed in table
sizing, see the hardware manual.
Ensure the cooling
See table
C
on page
allowed operating temperature range of the drive without derating is -15 to +40 °C.
EN
Protect the drive and input power cable
DA
See table
C
on page 96. Check that the operating time of the fuse is below 0.5
seconds.
DE
Install the drive on the wall
ES
See figures
A
and
FI
Check the compatibility with IT (ungrounded), corner-
FR
grounded delta, midpoint-grounded delta and TT systems
IT
The standard drive with ground-to-phase varistors connected can be installed to a
symmetrically grounded TN-S system. For other systems, see the hardware manual
NL
and ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor
disconnecting instructions (3AUA0000125152 [English]).
PT
RU
SV
TR
CN
96
for the losses and the cooling air flow through the drive. The
B
on page 95.
K
on page 98. For the conditions of the