Electrical Connections - Goodman GSZ140311 Installation & Service Reference

Table of Contents

Advertisement

To avoid possible explosion, the line from the
nitrogen cylinder must include a pressure
regulator and a pressure relief valve. The
pressure relief valve must be set to open at no
more than 450 psig.
Leak test the system using dry nitrogen and soapy
water to identify leaks. If you prefer to use an electronic
leak detector, charge the system to 10 PSIG with the
appropriate system refrigerant (see Serial Data Plate
for refrigerant identification). Do not use an alternative
refrigerant. Using dry nitrogen finish charging the system
to 450 PSIG. Apply the leak detector to all suspect areas.
When leaks are discovered, repair the leaks, and repeat
the pressure test. If leaks have been eliminated proceed to
system evacuation.
System Evacuation
Condensing unit liquid and suction valves are closed to
contain the charge within the unit. The unit is shipped with
the valve stems closed and caps installed. Do not open
valves until the system is evacuated.
REFRIGERANT UNDER PRESSURE!
Failure to follow proper procedures may cause
property damage, personal injury or death.
NOTE: Scroll compressors should never be used
to evacuate or pump down a heat pump or air
conditioning system.
Prolonged operation at suction pressures less
than 20 psig for more than 5 seconds will result
in overheating of the scrolls and permanent
damage to the scroll tips, drive bearings and
internal seal.
Deep Vacuum Method (Recommended)
The Deep Vacuum Method requires a vacuum pump
rated for 500 microns or less. This method is an effective
and efficient way of assuring the system is free of non-
condensable air and moisture. As an alternative, the Triple
Evacuation Method is detailed in the Service Manual for
this product model.
It is recommended to remove the Schrader Cores from the
service valves using a core-removal tool to expedite the
evacuation procedure.
WARNING
WARNING
CAUTION
1. Connect the vacuum pump, micron gauge, and
vacuum rated hoses to both service valves.
Evacuation must use both service valves to eliminate
system mechanical seals.
2. Evacuate the system to less than 500 microns.
3. Isolate the pump from the system and hold vacuum
for 10 minutes (minimum). Typically, pressure will rise
slowly during this period. If the pressure rises to less
than 1000 microns and remains steady, the system is
considered leak-free; proceed to system charging and
startup.
4. If pressure rises above 1000 microns but holds steady
below 2000 microns, non-condensable air or moisture
may remain or a small leak is present. Return to step
2: If the same result is achieved check for leaks and
repair. Repeat the evacuation procedure.
5. If pressure rises above 2000 microns, a leak is
present. Check for leaks and repair. Repeat the
evacuation procedure.
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
0
1

ELECTRICAL CONNECTIONS

HIGH VOLTAGE!
Disconnect ALL power before
servicing. Multiple power sources
may be present.
Failure to do so may cause property
damage, personal injury or death
due to electric shock. Wiring must
conform with NEC or CEC and all
local codes. Undersized wires could
cause poor equipment performance,
equipment damage or fire.
To avoid the risk of fire or equipment damage,
use copper conductors.
5
LEAK(S)
PRESENT
CONDENSIBLES OR SMALL
LEAK PRESENT
NO LEAKS
NO CONDENSIBLES
2
3
4
5
6
7
8
MINUTES
WARNING
WARNING
9
10

Advertisement

Table of Contents
loading

Table of Contents