DIAGNOSTIC
LEDs
DIP
SWITCHES
Integrated Control
EL280UH units are equipped with a two-stage integrated
control. This control manages ignition timing and fan off
delays based on selections made using the control DIP
switches. The control includes an internal watchguard fea
ture which automatically resets the integrated control when
it has been locked out. After one hour of continuous ther
mostat demand for heat, the watchguard will break and re
make thermostat demand to the furnace and automatically
reset the control to relight the furnace.
DIP Switch Settings
Switch 1 -- Thermostat Selection -- This unit may be
used with either a single-stage or two-stage thermostat.
The thermostat selection is made using a DIP switch which
must be properly positioned for the particular application.
The DIP switch is factory-positioned for use with a two-
stage thermostat. If a single-stage thermostat is to be used,
the DIP switch must be repositioned.
a - Select "OFF" for two-stage heating operation con
trolled by a two-stage heating thermostat (factory set
ting);
TWO-STAGE INTEGRATED
CONTROL
1/4" QUICK CONNECT TERMINALS
SENSE = 120 VAC OUTPUT TO FLAME SENSOR
NEUTRALS= 120 VAC NEUTRAL
PARK = DEAD TERMINAL FOR UNUSED BLOWER LEAD
HEAT LOW = 120 VAC OUTPUT TO CIRC BLWR -- LOW HT SPEED
HEAT HIGH/ COOL LOW = 120 VAC OUTPUT TO CIRC BLWR --
COOL HIGH = 120 VAC OUTPUT TO CIRC BLWR -- HIGH COOL SPEED
THERMOSTAT CONNECTIONS (TB1)
ON-BOARD
LINKS
1= ERROR CODE RECALL
H= 24V HUMIDIFIER OUTPUT
L= LENNOX SYSTEM OPERATION MONITOR
W915
DIP SWITCH(ES)
1 -- 2 Stage T'stat
W951
2 -- 2nd Stage Delay
3 & 4 -- Heat Off Delay
5 -- Cool Off Delay
FIGURE 30
Switch 2 -- Second Stage Delay (Used with Single-
Stage Thermostat Only) -- This switch is used to deter
mine the second stage on delay when a single-stage ther
mostat is being used. The switch is factory-set in the OFF
position, which provides a 10-minute delay before second-
stage heat is initiated. If the switch is toggled to the ON
position, it will provide a 15-minute delay before second-
stage heat is initiated. This switch is only activated when
the thermostat selector jumper is positioned for SINGLE-
stage thermostat use.
Switches 3 and 4 -- Heating Blower-Off Delay -- The
heating blower-on delay of 30 seconds is not adjustable.
The heating blower-off delay (time that the blower operates
after the heating demand has been satisfied) can be ad
justed by moving switches 3 and 4 on the integrated con
trol. The unit is shipped from the factory with a heating
blower-off delay of 90 seconds. The heating blower off
delay affects comfort and is adjustable to satisfy individual
applications. Adjust the blower off delay to achieve a sup
Page 28
HIGH HEAT AND LOW COOL SPEED
DIP SWITCH FUNCTIONS
Selects t/stat type (single or two-stage)
Second stage ON delay (single-stage t'stat)
Heating fan OFF delay
Cooling fan OFF delay
b - Select "ON" for two-stage heating operation con
trolled by a single-stage heating thermostat. This set
ting provides a timed delay before second-stage heat
is initiated.
FUNCTION