Summary of Contents for Helios HQ 200-710

  • Page 1 Helios Ventilatoren MONTAGE- UND BETRIEBSVORSCHRIFT INSTALLATION AND OPERATING INSTRUCTIONS NOTICE DE MONTAGE ET D’UTILISATION Axial-Hochleistungsventilatoren Axial high-performance fans Ventilateurs hélicoïdes à haut rendement Ø 200-710 mm HRF Ø 200-710 mm Ø 200-315 mm Ø 200-630 mm...
  • Page 2: Table Of Contents

    DEUTSCH Inhaltsverzeichnis KAPITEL 1 ALLGEMEINE HINWEISE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Seite 1 1.0 Wichtige Informationen .
  • Page 3: Wichtige Informationen

    Montage- und Betriebsvorschrift Axial-Hochleistungsventilatoren – HQ / HRF / HS / HW 1 .0 Wichtige Informationen KAPITEL 1 Zur Sicherstellung einer einwandfreien Funktion und zur eigenen Sicherheit sind alle nachstehenden Vorschriften genau durchzulesen und zu beachten. ALLGEMEINE HINWEISE Dieses Dokument ist Teil des Produktes und als solches zugänglich und dauerhaft aufzubewahren um einen sicheren Betrieb des Ventilators zu gewährleisten.
  • Page 4 Montage- und Betriebsvorschrift Axial-Hochleistungsventilatoren – HQ / HRF / HS / HW – Das Gerät ist gegen Wiedereinschalten zu sichern! – Nach dem Stillstand rotierender Teile ist eine Wartezeit von 3 Minuten einzuhalten, da durch interne Kondensatoren auch nach der Trennung vom Netz gefährliche Spannungen auftreten können! •...
  • Page 5: Garantieansprüche - Haftungsausschluss

    Alle Ausführungen dieser Dokumentation müssen beachtet werden, sonst entfällt die Gewährleistung. Gleiches gilt für Haftungsansprüche an Helios. Der Gebrach von Zubehörteilen, die nicht von Helios empfohlen oder angeboten werden, ist nicht statthaft. Eventuell auftretende Schäden unterliegen nicht der Gewährleistung. Veränderungen und Umbauten am Gerät sind nicht zulässig und führen zum Verlust der Konformität, jegliche Gewährleistung und Haftung...
  • Page 6: Leistungsdaten

    Axial-Hochleistungsventilatoren – HQ / HRF / HS / HW 1 .10 Leistungsdaten * (Leistungs- u. Geräuschangaben aus den aktuell gültigen Helios Druckschriften und Das Gerätetypenschild gibt über die verbindlichen elektrischen Werte Aufschluss; diese müssen mit dem örtlichen dem Internet) Versorgungsnetz abgestimmt sein. Die Ventilatorleistungen* wurden auf einem Prüfstand entspr. DIN EN ISO 5801 ermittelt;...
  • Page 7: Personalqualifikation

    Alle Ventilatoren vom Typ H..D können auf mindestens eine der nachfolgenden Weisen drehzahlgesteuert werden. a) Transformator/Phasenanschnitt: Für alle spannungssteuerbaren Ventilatortypen, sind die zugehörigen Steuergeräte den Helios Verkaufsunterlagen zu entnehmen. Ventilatortypen denen kein Steuergerät zugeordnet ist, sind nicht span- ACHTUNG nungssteuerbar. Eine Drehzahlregelung darf bei der Schaltart Y/Δ nur in der großen Stufe erfolgen .
  • Page 8: Konstruktiver Aufbau

    Montage- und Betriebsvorschrift Axial-Hochleistungsventilatoren – HQ / HRF / HS / HW 3 .0 Konstruktiver Aufbau KAPITEL 3 Baureihe HQ / HS / HW Die Ventilatortypen HQ (Abb.3) / HS / HW (Abb.4) bestehen aus einer Einbauplatte/-ring mit angeformter Einströmdüse, MONTAGE einem Elektromotor mit Befestigungsstreben, einem Laufrad dynamisch ausgewuchtet nach ISO 1940 T1, Klasse G 6,3 und einem Schutzgitter aus verzinktem Stahldraht gemäß...
  • Page 9: Montage - Einbau

    Ventilatoren die mit Flanschmotor (H..D 400/2/2; H..D 400/4/2; HRFD 450/2/2; HRFD 500/2/2; H..W 560/4; H..W 630/4; H..D 630/4/4; H..D 630/8/4; Ø710 außer H..W 710/6 & H..D 710/8) ausgestattet sind verfügen nicht über Kondenswasserlöcher, bei diesbezüglicher Verwendung ist eine Rücksprache mit Helios erforderlich. Nach Entfernen der Verpackung und vor Montagebeginn sind folgende Punkte zu überprüfen: –...
  • Page 10: Instandhaltung Und Wartung

    Montage- und Betriebsvorschrift Axial-Hochleistungsventilatoren – HQ / HRF / HS / HW Bei Problemen mit einem der oben aufgeführten Punkte, ist eine Wartung nach den Anweisungen aus Kapitel 4 durch- zuführen. KAPITEL 4 4 .0 Instandhaltung und Wartung Es sind die in Kapitel 1, Punkt 1 .2 aufgeführten Sicherheitshinweise zu beachten! –...
  • Page 11: Ersatzteile

    Nachströmung Nachströmungsöffnungen erweitern 4 .3 Ersatzteile Es sind ausschließlich Helios Originalersatzteile zu verwenden. Alle Reparaturen dürfen nur von autorisiertem/en Fach- personal/-Betrieben durchgeführt werden. 4 .4 Stilllegen und Entsorgen Es sind die in Kapitel 1, Punkt 1 .2 aufgeführten Sicherheitshinweise zu beachten!
  • Page 12: Abmessungen

    Montage- und Betriebsvorschrift Axial-Hochleistungsventilatoren – HQ / HRF / HS / HW KAPITEL 5 5 .0 Abmessungen Baureihe HQ ABMESSUNGEN Type Ø A Ø B iL . Ø G HQ.. 200 HQ.. 250 100/220 HQ.. 315 160/230 HQ.. 355 190/230 HQ..
  • Page 13 Montage- und Betriebsvorschrift Axial-Hochleistungsventilatoren – HQ / HRF / HS / HW SS-964 Einphasen-Wechselstrom mit TK U1 U2 U1 U2 TK TK TK TK 2 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9 SS-965 Einphasen-Wechselstrom 85159 001 SS-964 05.07.10...
  • Page 14 Montage- und Betriebsvorschrift Axial-Hochleistungsventilatoren – HQ / HRF / HS / HW SS-439 Einphasen-Wechselstrom SS-317 Einphasen-Wechselstrom mit TK SS-472 Drehstrom, 400V mit TK Y/YY Dahlander 32961 SS-472 30.06.10...
  • Page 15 Montage- und Betriebsvorschrift Axial-Hochleistungsventilatoren – HQ / HRF / HS / HW SS-475 Einphasen-Wechselstrom mit TK stromventilator tor with contacts ur monophasé rmocontacts. SS-520 Drehstrom, 400V, zweitourig mit TK 32483 SS-520 SS-469 Drehstrom, 400V mit TK SS-776 32955 SS-469 30.06.10 Drehstrom, 400V zweitourig mit KL...
  • Page 16 ENGLISH Table of Contents CHAPTER 1 GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1 1.0 Important information .
  • Page 17: Important Information

    Installation and Operating Instructions Axial high-performance fans – HQ / HRF / HS / HW 1 .0 Important information CHAPTER 1 In order to ensure complete and effective operation and for your own safety, all of the following instructions should be read carefully and observed.
  • Page 18 Installation and Operating Instructions Axial high-performance fans – HQ / HRF / HS / HW – Once the rotating parts come to a standstill, a waiting time of 3 min. must be observed, as dangerous voltages may be present due to internal capa- citors even after disconnection from the mains! •...
  • Page 19: Warranty Claims - Exclusion Of Liability

    All versions of this documentation must be observed, otherwise the warranty shall cease to apply. The same applies to liability claims against Helios. The use of accessory parts, which are not recommended or offered by Helios, is not per- mitted. Any possible damages are not covered by the warranty. Changes and modifications to the unit are not permitted and lead to a loss of conformity, and any warranty and liability shall be excluded in this case.
  • Page 20: Noise Data

    1 .11 Noise data * (performance and noise data from the currently valid Helios publications and the internet) The noise data* also refers to the aforementioned directive. Housing variations, unfavourable operating conditions and many other things can lead to an increase in the specified catalogue values. Data that refers to certain distances (1, 2, 4 m) apply to free field conditions.
  • Page 21: Chapter 2 General Operating Instructions

    All fans of type H..W can be voltage-controlled by means of transformer or phase control. The relevant controllers can be found in the Helios sales documents. With regard to the dimensioning of the controller, the maximum current for the speed control must be observed according to the type plate.
  • Page 22: Chapter 3 Installation

    Installation and Operating Instructions Axial high-performance fans – HQ / HRF / HS / HW 3 .0 Design CHAPTER 3 Series HQ / HS / HW The fan types HQ (Fig.3) / HS / HW (Fig.4) consist of a mounting plate/ring with integrated inlet nozzles, an electric INSTALLATION motor with mounting struts, a dynamically balanced impeller according to ISO 1940 T1, class G 6,3 and a protection guard made of galvanised steel wire pursuant to DIN EN ISO 13857 (HQ, HW) respectively made of plastics (HS).
  • Page 23: Installation - Assembly

    Fans which are equipped with flange motors (H..D 400/2/2; H..D 400/4/2; HRFD 450/2/2; HRFD 500/2/2; H..W 560/4; H..W 630/4; H..D 630/4/4; H..D 630/8/4; Ø710 except H..W 710/6 & H..D 710/8) do not have condensation drain holes, consultation with Helios is necessary for such use. – is there any transport damage, –...
  • Page 24: Chapter 4 Servicing And Maintenance

    Installation and Operating Instructions Axial high-performance fans – HQ / HRF / HS / HW 4 .0 Servicing and maintenance CHAPTER 4 m The safety instructions specified in Chapter 1, section 1 .2 must be observed! – The units are basically maintenance-free, there is no provision for user-maintenance. Nevertheless, all necessary SERVICING AND maintenance work must be carried out by authorised specialist personnel cf.
  • Page 25: Spare Parts

    Clean Insufficient backflow Enlarge backflow openings 4 .3 Spare parts Only original Helios spare parts are to be used. Repairs may only be carried out by authorised specialist personnel/companies. 4 .4 Standstill and disposal ATTENTION m The safety instructions specified in Chapter 1, section 1 .2 must be observed! m The fan must be (all poles) disconnected from the mains power supply before disassembly! –...
  • Page 26: Chapter 5 Dimensions

    Installation and Operating Instructions Axial high-performance fans – HQ / HRF / HS / HW CHAPTER 5 5 .0 Dimensions Series HQ DIMENSIONS Type Ø A Ø B iL . Ø G direction of flow HQ.. 200 HQ.. 250 100/220 HQ..
  • Page 27 Installation and Operating Instructions Axial high-performance fans – HQ / HRF / HS / HW SS-964 Single-phase alternating currentwith TK U1 U2 U1 U2 TK TK TK TK 2 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9 SS-965 Single-phase alternating...
  • Page 28 Installation and Operating Instructions Axial high-performance fans – HQ / HRF / HS / HW SS-439 Single-phase alternating current SS-317 Single-phase alternating current with TK SS-472 Rotating current, 400V with TK Y/YY Dahlander 32961 SS-472 30.06.10...
  • Page 29 Installation and Operating Instructions Axial high-performance fans – HQ / HRF / HS / HW SS-475 Single-phase alternating current with TK stromventilator tor with contacts ur monophasé rmocontacts. SS-520 Rotating current, 400V, two-speed with TK 32483 SS-520 SS-469 Rotating current, 400V with TK 32955 SS-469 30.06.10 SS-776...
  • Page 30 FRANÇAIS Sommaire CHAPITRE 1 INFORMATIONS GÉNÉRALES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1 1.0 Informations importantes.
  • Page 31: Informations Importantes

    évite que les cheveux se prennent dans les pièces rotatives. Des dispositions particulières sont applicables pour l’utilisation, le raccorde- ment et le fonctionnement : contacter Helios Ventilateurs en cas de doute. Veiller à bien respecter les normes nationales, règlements de sécurité et instructions.
  • Page 32 Montage- und Betriebsvorschrift Ventilateurs hélicoïdes à haut rendement – HQ / HRF / HS / HW • Toutes les consignes de sécurité sont à respecter ! Respecter également les réglementations locales spécifiques ! • La protection contre tout contact accidentel répond à la norme DIN EN 13857 et doit être respectée par l’utilisateur (voir section 2.1) ! Tout contact avec les parties rotatives doit être évité.
  • Page 33: Garantie - Réserves Du Constructeur

    à des contraintes techniques et électroniques, l’accord de Helios est indispensable : les modèles standards n’étant plus appropriés pour cet usage. Idem pour une utilisation mobile des ventilateurs (voitures, avions, bateaux, etc.).
  • Page 34: Performances

    La plaque signalétique du ventilateur indique la puissance électrique requise ; l’appareil doit être raccordé à l’alimenta- Internet Helios. tion électrique locale. Les vitesses du ventilateur* ont été testées selon la norme DIN EN ISO 5801 ; elles s’appliquent au courant nominal et à...
  • Page 35: Qualification Du Personnel

    Tous les modèles de type H..W peuvent être régulés via transformateur ou hachage de phase. Les appareils de contrôle adéquats se commandent auprès de Helios Ventilateurs. Le courant max. à considérer lors du dimensionnement de la commande de vitesse est indiqué sur la plaque signalétique.
  • Page 36: Composition Du Ventilateur

    Montage- und Betriebsvorschrift Ventilateurs hélicoïdes à haut rendement – HQ / HRF / HS / HW 3 .0 Composition du ventilateur CHAPITRE 3 Série HQ / HS / HW Les modèles de ventilateurs HQ (fig. 3) / HS / HW (fig. 4) se composent d’une platine murale avec pavillon d’aspiration MONTAGE monté, un moteur électrique avec attaches de montage, une hélice équilibrée selon la norme ISO 1940 T1, classe G 6,3 et une grille de protection en fil de fer galvanisé...
  • Page 37: Montage - Installation

    – De fortes vibrations et/ou un bruit excessif peuvent provenir d’une utilisation hors de la plage de fonctionnement du ventilateur. Si tel est le cas, contacter impérativement Helios Ventilateurs ! – Pour un refroidissement suffisant du moteur, il est nécessaire d’assurer un débit minimal en fonction des gaines (fournitures client), de la pression du vent, etc.
  • Page 38: Nettoyage

    Montage- und Betriebsvorschrift Ventilateurs hélicoïdes à haut rendement – HQ / HRF / HS / HW – Pour la garantie d’un bon fonctionnement, les points suivants sont à vérifier : • Poussières ou saletés présentes sur le moteur et/ou l’hélice. •...
  • Page 39: Pièces De Remplacement

    Renouvellement d’air insuffisant. Amplifier le renouvellement d’air. 4 .3 Pièce de remplacement Les pièces de remplacement doivent exclusivement être fournies par Helios. Toute réparation doit être effectuée par un personnel certifié et qualifié. 4 .4 Arrêts et recyclage Respecter les consignes de sécurité du chapitre 1, section 1 .2 ! ATTENTION Avant le démontage, veiller à...
  • Page 40: Mesures

    Montage- und Betriebsvorschrift Ventilateurs hélicoïdes à haut rendement – HQ / HRF / HS / HW CHAPITRE 5 5 .0 Mesures Série HQ MESURES Sens de l’air Type Ø A Ø B iL . Ø G HQ.. 200 HQ.. 250 100/220 HQ..
  • Page 41 Montage- und Betriebsvorschrift Ventilateurs hélicoïdes à haut rendement – HQ / HRF / HS / HW SS-964 Courant alternatif monophase avec TK U1 U2 U1 U2 TK TK TK TK 2 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9 SS-965 Courant alternatif...
  • Page 42 Montage- und Betriebsvorschrift Ventilateurs hélicoïdes à haut rendement – HQ / HRF / HS / HW SS-439 Courant alternatif SS-317 Courant alternatif monophase avec TK SS-472 Courant triphasé, 400 V avec TK Y/YY Dahlander 32961 SS-472 30.06.10...
  • Page 43 Montage- und Betriebsvorschrift Ventilateurs hélicoïdes à haut rendement – HQ / HRF / HS / HW SS-475 Courant alternatif monophase avec TK stromventilator tor with contacts ur monophasé rmocontacts. SS-520 Vitesse de rotation, 400 V avec TK, 2 vitesses 32483 SS-520 SS-469 Courant triphasé, 400 V avec TK...
  • Page 44 HELIOS Ventilatoren GmbH + Co KG · Lupfenstraße 8 · 78056 VS-Schwenningen HELIOS Ventilateurs · Le Carré des Aviateurs · 157 av. Charles Floquet · 93155 Le Blanc Mesnil Cedex CH HELIOS Ventilatoren AG · Tannstrasse 4 · 8112 Otelfingen GB HELIOS Ventilation Systems Ltd.