METREL test and measurement accessories: EVSE adapter A 1532 XA Instruction manual Version 1.1.1, Code no. 20 753 114...
Page 2
The trade names Metrel , Smartec , Eurotest , Auto Sequence are trademarks registered in Europe and other countries. No part of this publication may be reproduced or utilized in any form or by any means without permission in writing from METREL.
Safety and operational considerations ..............5 Warnings and notes ..................5 Markings on the adapter ..................5 Standards applied ..................... 6 Adapter description ....................7 A 1532 XA operation ....................8 Maintenance ......................12 Cleaning ......................12 Service ......................12 Technical specifications ..................13...
Vehicle Supply Equipment (EVSE) to test socket of installation tester for verification of electrical safety and functional testing, inclusive load test. It is intended for testing Mode 3 EV supply equipment with type 2 connector. A 1532 XA EVSE adapter is a special accessory intended to be used with METREL installation testers.
care for safe operation«. The symbol requires an action! If the A 1532 XA is used in a manner not specified in this Instruction manual or the Instruction manual of target test equipment, the protection provided by the A 1532...
A 1532 XA EVSE adapter Safety and operational considerations 2.3 Standards applied The A 1532 XA adapter is manufactured and tested in accordance with the following regulations: Safety (LVD) Safety requirements for electrical equipment for measurement, control EN 61010 - 1 and laboratory use –...
A 1532 XA EVSE adapter Adapter description 3 Adapter description Figure 3.1: A 1532 XA components Legend: Banana socket outputs for connection to 3-phase installation tester or load Banana socket outputs are intended for test purposes only! Voltage on EVSE output indicators...
A 1532 XA EVSE adapter A 1532 XA operation 4 A 1532 XA operation Connections Figure 4.1: A 1532 XA connection to EVSE and Metrel installation tester – safety tests Figure 4.2: A 1532 XA connection to EVSE – functional tests...
Page 9
A 1532 XA operation Figure 4.3: A 1532 XA connection to EVSE and test load – load test Safety and functional tests: Connect the A 1532 XA output to the installation tester (via mains test socket or via safety banana sockets) Set PP STATE (3) to position N.C.
Page 10
EVSE is supplying energy only if ventilation exists. Recommended sequences: A-B-C for non-ventilated charging A-B-D for charging with ventilation required Note: With A 1532 XA alone only proximity pilot and control pilot functions of EVSE can be checked. Fault simulation options Push Fault Comment...
Page 11
A 1532 XA EVSE adapter A 1532 XA operation Notes: If the input resistance is 1 MΩ instead of recommended 10 MΩ, the measured signal amplitude is approx. 17 % lower than actual value. Oscilloscope probe shall be compensated to get proper frequency response.
5.1 Cleaning No special maintenance is required for the housing. To clean the surface of the adapter, use a soft cloth slightly moistened with soapy water or alcohol. Then leave the A 1532 XA to dry totally before use. Warnings: Do not use liquids based on petrol or hydrocarbons! ...
A 1532 XA EVSE adapter Technical specifications 6 Technical specifications 6.1 General data Input voltage .......... up to 250 V (1-phase), up to 430 V (3-phase) Frequency ..........50 Hz, 60 Hz Maximum test current ......267 A (10 ms) intermittent operation Maximum load current ......