R−410A QUICK REFERENCE GUIDE
S
R−410A refrigerant operates at 50−70 percent higher pressures than R−22. Be sure that servicing equipment and replacement
components are designed to operate with R−410A refrigerant.
S
R−410A refrigerant cylinders are rose colored.
S
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
S
R−410A refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold
hose when charging into suction line with compressor operating
S
Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low−side retard.
S
Use hoses with 700 psig service pressure rating.
S
Leak detectors should be designed to detect HFC refrigerant.
S
R−410A refrigerant, as with other HFCs, is only compatible with POE oils.
S
Vacuum pumps will not remove moisture from oil.
S
Do not use liquid−line filter driers with rated working pressures less than 600 psig.
S
Do not leave R−410A refrigerant suction line filter driers in line longer than 72 hours.
S
Do not install a suction−line filter drier in liquid line.
S
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
S
POE oils may cause damage to certain plastics and roofing materials.
S
Wrap all filter driers and service valves with wet cloth when brazing.
S
A factory approved liquid−line filter drier is required on every unit.
S
Do NOT use an R−22 TXV.
S
If indoor unit is equipped with a R−22 TXV or piston metering device, it must be changed to a hard−shutoff R−410A refrigerant
TXV.
S
Never open system to atmosphere while it is under a vacuum.
S
When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter
driers. Evacuate to 500 microns prior to recharging.
S
Do not vent R−410A refrigerant into the atmosphere.
S
Do not use capillary tube coils.
S
Observe all warnings, cautions, and bold text.
My Learning Center is your central location for professional residential HVAC training resources that help strengthen careers and businesses.
We believe in providing high quality learning experiences both online and in the classroom.
Access My Learning Center with your HVACpartners credentials at MLCtraining.com. Please contact us at mylearning@utc.com with
questions.
Copyright 2019 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
TRAINING
Edition Date: 6/19
12
Catalog No: IM-FB4C-FX4D-02
Replaces: IM-FB4C-FX4D-01

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fb4cnfFx4d

Table of Contents