UPS Parameters (Strato Pi UPS only)

In its factory default configuration, Strato Pi UPS doesn't automatically power down the
Raspberry Pi when the main power source is not available.
It is the user application that, after being notified that the it is running on battery power via
the BatteryPower pin, will have to initiate a delayed power-cycle setting the
ShutdownEnable pin to high.
This can be changed with the XUBnnnnn command.

XUBnnnnn - UPS automatic power off (*)

Set the UPS automatic power-off timer.
Command
Description
XUBnnnnn
Set the UPS automatic power off timeout, in seconds. Strato Pi
UPS will automatically initiate a delayed power-cycle (just like
when GPIO16 is set high) if the main power source is not
available for the number of seconds set with this command. Min:
1; Max: 99999
XUB00000
UPS automatic power off disabled (factory default)
XUB?
Return current UPS automatic power off configuration