Finishing; Connection Pipe, Cable And Drain Hose - Fujitsu AirStage AG A012GCGH Series Installation Manual

Indoor unit (floor type)
Hide thumbs Also See for AirStage AG A012GCGH Series:
Table of Contents

Advertisement

● Forced thermostat off function
["Edge" input only]
Function
Connector
setting
Ch3 of CNA03 or
60-00
CNA04
● Refrigerant leak detection function (only for J-IIIL series)
["Edge" input only]
Function
Connector
setting
Ch3 of CNA03 or
60-09
CNA04
5.6.2 External output
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• Output voltage: Hi DC12V±2V, Lo 0V.
• Permissible current: 50mA
Output select
● When indicator etc. are connected directly
Operation indicator
Error indicator
Indoor unit Fan
status indicator
Connected unit
● When connecting with unit equipped with a power supply
Connected
device 1
Connected
device 2
Connected
device 3
Connected unit
Relay (locally purchased)
Operation behavior
Connector
Output voltage
External output 1
Pins 1-2
External output 2
CNB01
Pins 1-3
External output 3
Pins 1-4
Input signal
Command
OFF → ON
Thermostat off
ON → OFF
Normal
Input signal
Command
OFF → ON
No command
ON → OFF
Refrigerant leak
P.C.B
P.C.B
Status
0V
Stop
DC 12 V
Operation
0V
Normal
DC 12 V
Error
0V
Indoor unit fan stop
DC 12 V
Indoor unit fan operation

6. FINISHING

After checking for gas leaks (refer to the installation manual of the outdoor unit), perform
this section.
Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do
so may cause water leaks.

6.1. Connection pipe, cable and drain hose

(1) Insulate between pipes.
• Overlap the connection pipe heat insulation and indoor unit pipe heat insulation.
• Wrapping the connection pipe with cloth tape over the range within which they fit into the
rear piping housing section.
• Fasten the pipe bracket with the screw.
(2) Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain
water and wind cannot blow in.
(3) Fasten the drain hose to the outside wall, etc.
Insulation of indoor
unit pipes
There
are no
gaps
Overlap
CNB
01
Insulation of
refrigerant pipes
Left piping
Cable
Pipe
Drain hose
CNB
01
Fill the gap between the
knockout hole of the indoor
unit and the pipe or cable
with putty.
Check the following:
GOOD
Stopping
downward
End of drain hose
is immersed in
water.
Drainage
channel
CAUTION
Cloth
Wrap the pipes
tape
with cloth tape
Pipe
bracket
There are no gaps
Screw
For connection from the left rear
Cable
Wall pipe
Drain hose
Putty
PROHIBITED
Accumulated
No upward
drain water
slope
50 mm or less
from ground
Cable
Right side of
pipe bracket
Connection
pipe
Putty
Air
No
upward
slope
En-10