Field Setting; Setting The Address; Custom Code Setting; Function Setting - Fujitsu AirStage AG A012GCGH Series Installation Manual

Indoor unit (floor type)
Hide thumbs Also See for AirStage AG A012GCGH Series:
Table of Contents

Advertisement

7. FIELD SETTING

There are 3 methods for address setting by field setting as follows.
Please set by either of the methods.
Each setting method is described in below (1) to (3).
(1) IU AD, REF AD SW settings: This section (7.1. Setting the address)
(2) Remote controller settings:
(3) Automatic address settings: Refer to the outdoor unit manual for detailed setting

7.1. Setting the address

Manual address setting method
The indoor unit address and the refrigerant circuit address can also be set up through the
wireless remote controller
Be sure to turn OFF the power before performing the field setting.
• Please set it according to
• Position and detail of the switches
the following procedures
when setting manually.
CAUTION
Use an insulated
screwdriver to set the dip
switches.
Be careful not to make
mistakes for switch
settings.
Indoor unit
• Rotary switch (IU AD × 1)...Factory setting "0"
address
• Rotary switch (IU AD × 10)...Factory setting "0"
When connecting multiple indoor units to 1 refrigerant system, set the
address at IU AD SW as shown in the table A.
Refrigerant
• Rotary switch (REF AD × 1)...Factory setting "0"
circuit address
• Rotary switch (REF AD × 10)...Factory setting "0"
In the case of multiple refrigerant systems, set REF AD SW as shown
in the table A for each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
• If working in an environ-
Table A
ment where the wireless
remote controller can be
Address
used, the addresses can
also be set using the
Refrigerant
remote controller.
circuit
• If setting the address-
es using the wireless
remote controller, set
the indoor unit address
and refrigerant circuit
address to "00".
(For information on set-
ting using the wireless
remote controller.)
* Do not set the indoor
unit address (IU AD
10
SW) at 64 to 99.
11
It may result in failure.
99
Setting example
Setting
Setting
range
Indoor unit address
0 to 63
Refrigerant circuit
0 to 99
address
En-11
Refer to the wired or wireless remote controller manual
for detailed setting information. (Set IU AD, REF AD
SW to 0)
information. (Set IU AD, REF AD SW to 0)
CAUTION
For indoor unit
address
For refrigerant
circuit address
Rotary switch
Address
setting
REF AD SW
Indoor unit
× 10
× 1
0
0
0
0
1
0
1
1
2
0
2
2
3
0
3
3
4
0
4
4
5
0
5
5
1
0
10
1
1
11
9
9
63
Type of switch
Setting example
2
IU AD × 10
Setting example
63
REF AD × 10

7.2. Custom code setting

• Selecting the custom code prevents the indoor unit mix-up. (figure below)
(Up to 4 codes can be set.)
• Perform the setting for both the indoor unit and the remote controller.
Indoor unit
Remote
controller
• Custom code setting for indoor unit
Set the DIP switch SET3 SW1, 2, referring to the figure and table below.
DIP switch
"SET3"

7.3. Function setting

Please make this setting after completing all construction works.
• Function setting can be performed with the wired or wireless remote controller. (The
remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Rotary switch
setting
Function details
IU AD SW
Function
Function
number
× 10
× 1
Filter
0
0
indicator
0
1
interval
0
2
0
3
Filter
0
4
indicator
0
5
action
1
0
(Prohibited)
1
1
Vertical
airflow
direction
6
3
Horizontal
swing
airflow
direction
(Prohibited)
Cool air
tempera-
ture trigger
IU AD × 1
Heat air
tempera-
ture trigger
REF AD × 1
Auto restart
Confusion
DIP switch
"SET3"
DIP switch
A (Factory
SET3
SW1
SW2
WARNING
Setting number Default
Adjust the filter cleaning interval noti-
00 Standard
fication. If the notification is too early,
01 Longer
11
change to setting 01. If the notifica-
02 Shorter
tion is too late, change to setting 02.
Enable or disable the filter indicator.
00 Enable
Setting 02 is for use with a central
01 Disable
remote controller.
Display
13
only on
02
central
remote
controller
20
00
Adjust the vertical airflow direction.
00 Standard
23
01 Adjust
Adjust the horizontal swing airflow
00 Standard
direction.
01 Left half
24
(For horizontal swing equipped
02 Right half
models)
27
00
Adjust the cool air trigger tempera-
00 Standard
ture. To lower the trigger temperature,
01 Adjust (1)
30
use setting 01. To raise the trigger
02 Adjust (2)
temperature, use setting 02.
Adjust the heat air trigger
00 Standard
temperature. To lower the trigger tem-
01 Adjust (1)
perature by 6 degrees C, use setting
02 Adjust (2)
31
01. To lower the trigger temperature
by 4 degrees C, use setting 02. To
03 Adjust (3)
raise the trigger temperature, use
setting 03.
00 Enable
Enable or disable automatic system
restart after a power outage.
* Auto restart is an emergency func-
40
01 Disable
Code change
A
B
C
D
A
B
C
D
OFF
ON
SW 1
SW 2
SW 3
SW 4
Custom code
B
C
D
setting)
OFF
ON
OFF
ON
OFF
OFF
ON
ON
Details
tion such as for power failure etc.
Do not start and stop the indoor unit
by this function in normal operation.
Be sure to operate by the control
unit, converter or external input
device.