10-2. Back up/import settings data

The settings data that have been made from the Initial Setting Tool, Integrated Centralized Control Web, or Web
Browser for Initial Settings can be exported to an HDD as a backup.
The exported data can be imported back to the TE-200/TE-50/TW-50 to restore the previous settings after
TE-200/TE-50/TW-50 replacement. The settings data can be backed up or imported from the Integrated Centralized
Control Web or Web Browser for Initial Settings.
10-2-1. Integrated Centralized Control Web
(1) Enter the web page address in the address field of the Web browser as follows:
http://[IP address of the login destination TW-50]/control/index.html
Note: The web page will be displayed in the same language as the operating system on the PC.
The web page can be displayed in other languages by entering the web page address as follows:
Chinese
English
French
German
Italian
Japanese
Portuguese
Russian
Spanish
Turkish
(2) Click [Maintenance] > [Utility] > [Back up/import settings data] to access the Back up/import settings data
screen.
Note: This function is accessible only if logged in as a building manager. Tenant managers and general users cannot
use this function.
Reference
Click to browse for a file
that contains the data to be
imported.
Data import source
The path to the file to be
imported will appear.
WT09308X01
http://[IP address of TW-50]/control/index.html?zh
http://[IP address of TW-50]/control/index.html?en
http://[IP address of TW-50]/control/index.html?fr
http://[IP address of TW-50]/control/index.html?de
http://[IP address of TW-50]/control/index.html?it
http://[IP address of TW-50]/control/index.html?ja
http://[IP address of TW-50]/control/index.html?pt
http://[IP address of TW-50]/control/index.html?ru
http://[IP address of TW-50]/control/index.html?es
http://[IP address of TW-50]/control/index.html?tr
31
Back up settings data
Click to back up the TW-50
settings data.
Import settings data
Click to import the file
specified in the "Data import
source" field to the TW-50.