410 Parameters
No.
Name/Value
94.11
LSU stop delay
0.0 ... 3600.0 s
94.20
DC voltage
reference
0.0 ... 2000.0 V
94.21
DC voltage ref
source
Zero
User ref
Other
94.22
User DC voltage
reference
0.0 ... 2000.0 V
94.30
Reactive power
reference
-3276.8 ... 3276.7
kvar
94.31
Reactive power ref
source
Zero
User ref
Other
94.32
User reactive power
reference
-3276.8 ... 3276.7
kvar
94.40
Power mot limit on
net loss
0.00 ... 600.00%
Description
Defines a stop delay for the supply unit. This parameter can
be used to delay the opening of the main breaker/contactor
when a restart is expected.
Supply unit stop delay.
(Only visible when IGBT supply unit control activated by
95.20)
Displays the DC voltage reference sent to the supply unit.
This parameter is read-only.
DC voltage reference sent to supply unit.
(Only visible when IGBT supply unit control activated by
95.20)
Selects the source of the DC voltage reference to be sent to
the supply unit.
None.
94.22 User DC voltage
reference.
Source selection (see
Terms and abbreviations
(Only visible when IGBT supply unit control activated by
95.20)
Defines the DC voltage reference for the supply unit when
94.21 DC voltage ref source
User DC reference.
(Only visible when IGBT supply unit control activated by
95.20)
Displays the reactive power reference sent to the supply unit.
This parameter is read-only.
Reactive power reference sent to the supply unit.
(Only visible when IGBT supply unit control activated by
95.20)
Selects the source of the reactive power reference to be sent
to the supply unit.
None.
94.32 User reactive power
Source selection (see
Terms and abbreviations
(Only visible when IGBT supply unit control activated by
95.20)
Defines the reactive power reference for the supply unit when
94.31 Reactive power ref source
User reactive power reference.
Defines the maximum shaft power for motoring mode upon a
supply network failure when IGBT supply unit control is active
(bit 15 of
95.20 HW options word 1
The value is given in percent of nominal motor power.
Note: With a diode supply unit (bit 11 of
motoring shaft power is limited to 2% upon a network failure
regardless of this parameter.
Maximum shaft power for motoring mode upon a supply
network failure.
on page 114). -
is set to
User
ref.
reference.
on page 114). -
is set to
User
ref.
is on).
95.20
is on), the
Def/FbEq16
600.0 s
10 = 1 s
-
10 = 1 V
User ref
0
1
0.0 V
10 = 1 V
-
10 = 1 kvar
User ref
0
1
0.0 kvar
10 = 1 kvar
600.00%
1 = 1%