8-3. FAN OPERATION
RETURN SELECT
MENU
HOLD
.
Control Mode
1. Temperature
Set by remote controller.
adjustment
function
4 speeds + Auto type
When [Auto] is set, fan speed becomes [Low].
2. Drain pump
2-1. Drain pump control
The drain pump turns ON for the specified amount of time when any of the following
conditions has been satisfied:
1 ON for 3 minutes after the operation mode is switched from COOL or DRY to another
operation mode (FAN).
2 ON for 6 minutes after the float switch is submerged in the water when the float switch
control judges the sensor is in the water.
2-2. Float switch control
• Float switch control judges whether the sensor is in the air or in the water by turning the
float switch ON/OFF.
In the water: Detected that the float switch is ON for 15 seconds.
In the air: Detected that the float switch is OFF for 15 seconds.
3. Vane
Same as the control performed during the COOL operation, but with no restriction on the vane's
(up/down vane
downward blow setting
position change)
OCHT746A
<How to operate>
1 Press ON/OFF button.
2 Press [F1] button to display FAN.
ON
OFF
<How to operate>
1 Press POWER ON/OFF button.
2 Press the operation MODE button to display FAN.
Control Details
Type
Auto
Fan speed notch
27
Remarks
• Operates as it would
in COOL operation.