Information for use in USA / Canada
Enclosure
Intended use
Power source
Cable assemblies
Conductor size
Directives / Harmonized Standards
EN 61508:2010
EN 62061:2021
EN ISO 13849-1:2015
EN ISO 14119:2013
Certificates
2TLC172271M0201
Rev.H
Type 1, 4, 4x
Applications according to NFPA 79
Only suitable for use in a limited voltage / current circuitry.
The limited voltage / current source must comply with one of the
following:
a) An isolating device such that the maximum open circuit voltage
potential available to the circuit is not more than +24 VDC and
the current is limited to a value not exceeding 8 A measured after
1 min of operation.
or
b) A suitable isolating source in conjunction with a fuse in
accordance with UL248. The fuse shall be rated max. 4 A and be
installed in the +24 VDC power supply to the device to limit the
available current.
Any listed (CYJV/7), M12, 4-pin or 5-pin, A-coding mating connector. Cord
provided shall be 24 AWG (0.2 mm
with leads for connection to the source, 30 AWG (0.05 mm
when connectors are provided on both ends.
Maximum ampere ratings of the overcurrent protection:
2
AWG
(mm
)
Ampere
22
(0.32)
3
24
(0.20)
2
26
(0.13)
1
28
(0.08)
0.8
30
(0.05)
0.5
-9
SIL3, PFH
= 4.5 x 10
D
SIL3
PL e, category 4
Type 4, high level coded, (Eva Unique code)
Type 4, low level coded, (Eva General code)
TÜV Süd, cULus
2
) minimum when one end is provided
2
) minimum
30