3.4

Calculation of the operating point

In connection with a Helios hot water heating element WHR.., the following guide values for the differential pressure
setpoint are approximated:
Type
Water
Line cross-
section
WHR
volume
250
470 l/h
315
810 l/h
355
1080 l/h
400
1060 l/h
2/40/20
610 l/h
4/40/20
980 l/h
2/50/25-30 1050 l/h
* The pressure loss in the piping depends on the pipe length, pipe diameter and the water flow rate!
- Technical Data
Permitted pumping media (other media on
request)
Performance
Max. delivery head (Hmax)
Max. flow rate (Qmax)
Permitted range of application
Installation location requirements
Connection voltage
Protection category
Energy efficiency index EEI
Max. operating pressure
Minimum inlet pressure at +95 °C/+110 °C
4.1

Maintenance and servicing

The safety instructions in chapter 1.3 must be observed!
– It must be ensured that the assembly has been disconnected from the mains power before any work!
– In principle, the assemblies are maintenance-free, user maintenance is not envisaged.
However, any necessary maintenance work must be carried out by authorised, qualified personnel!
After maintenance and servicing work, the following must be checked:
• fittings, water connections and pipes are tightly fitted
4.2

Spare parts

Only Helios original spare parts must be used. All repairs must only be carried out by authorised, qualified personnel/
companies.
4.3

Decommissioning and disposal

Dispose of the components used according to the locally applicable regulations and laws.
Press. loss
Press. loss*
pipe [kPa]
WHR [kPa]
3/4"
8
8
3/4"
9
8
3/4"
9
10
3/4"
11
10
3/4"
10
8
3/4"
7
10
3/4"
7
10
Heating water (pursuant to VDI 2035) water-glycol mixtures (max.
1:1; the performance data must be reviewed over 20 % admixture)
6,0 m
3,6 m
3
/h
5 - 50°C < 90% RH non-condensing
1 ~ 230 V +10 %/ -15 %, 50/60 Hz (as per IEC 60038)
IP X4D
See type plate
10 bar (1000 kPa)
0.5 bar/ 1.0 bar (50 kPa/ 100 kPa)
11
Fig. 18
Press. loss
Press. loss
Different. press.
setpoint pump
WHSH [kPa]
total [kPa]
3.5
19.5
4.5
21.5
5.5
24.5
5.5
26.5
4
22
5
22
5.5
22.5
EN
2.0 m
2.2 m
2.5 m
2.7 m
2.2 m
2.2 m
2.5 m