PowMr SOLXPOW X2 Series User Manual

PowMr SOLXPOW X2 Series User Manual

Hybrid inverter

Advertisement

Quick Links

User Manual
SOLXPOW X2 Series & SOLXPOW X3 Series

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SOLXPOW X2 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for PowMr SOLXPOW X2 Series

  • Page 1 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series...
  • Page 3: Important Safety Instructions

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Important Safety Instructions Please save these instructions for future use! Read all of the instructions and cautions in the manual before beginning the installation! ⚫ Before installation, please read this manual carefully and follow the instructions in this manual strictly.
  • Page 4 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Symbols On the Inverter Symbol Description To avoid the potential effects on the environment and human health as a result of the presence of hazardous substances in electrical and electronic equipment, end-users of electrical and electronic equipment should understand the meaning of the crossed-out wheeled bin symbol.
  • Page 5: Table Of Contents

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Table of Contents Important Safety Instructions ......................1 Symbols On the Inverter ......................2 1 About This Manual ........................3 1.1 How To Use This Manual ....................3 1.2 Target Groups ........................3 1.3 Symbols ...........................
  • Page 6: Symbols On The Inverter

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 6 Operation ........................... 45 6.1 Operation Modes ......................45 6.2 Back-Up and Off-Grid Output ..................50 6.3 Main Window ......................... 51 6.4 General Setting ......................52 6.5 Advanced Setting ......................54 6.6 Country Code (Safety Code) Setting ................
  • Page 7: About This Manual

    SOLXPOW X2 Series & SOLXPOW X3 Series 1 About This Manual This manual is an integral part of PowMr SOLXPOW X2 series and SOLXPOW X3 series single- phase high-voltage hybrid inverters (hereinafter referred to as the inverter). It mainly introduces the assembly, installation, electrical connection, debugging, maintenance and troubleshooting of the products.
  • Page 8: Statement

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 1.4 Statement Our company has the right not to undertake quality assurance in any of the following circumstances: ⚫ Damages caused by improper transportation. ⚫ Damages caused by incorrect storage, installation or use.
  • Page 9: Product Description

    2 Product Description 2.1 Product Introduction The PowMr SOLXPOW X2 series and SOLXPOW X3 series inverter is also known as hybrid inverter or storage inverter, which is mainly used to combine the PV array, lithium battery, loads and power grid to realize intelligent power management and dispatching.
  • Page 10: Product Features

    The applicable grid types for the PowMr SOLXPOW X2 series and SOLXPOW X3 series are TN-S, TN-C, TN-C-S and TT. When applied to the TT grid, the voltage of N to PE suggests less than 30V.
  • Page 11: Appearance

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 2.4 Appearance Figure 2-3 Inverter Appearance Wiring terminals are at the bottom of the inverter, as shown in the table below. Item Terminal Note Display the operation information and working status Display and LED panel of the inverter.
  • Page 12: Indicator

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 2.5 Indicator Figure 2-4 Inverter display interface Item Indicator Status Description Grid lost. Slow Grid Indicator Inverter detected grid but not running in on-grid mode. flashing Always on Inverter works in on-grid mode.
  • Page 13: Installation

    The device is thoroughly tested and strictly inspected before delivery. Nonetheless, damage may still occur during shipping. For this reason, please conduct a thorough inspection after receiving the device. Contact PowMr or the transport company in case of any damage or incompleteness, and provide photos to facilitate services. 3.2 Packing List The package of the inverter includes the following accessories.
  • Page 14 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Figure 3-1 Packing list Item Name and Quantity Note Inverter (1pcs) Wall-mounting bracket (1pcs), Expansion plug set (5pcs), M5 screws (1pcs) On-grid connector set (1pcs) Back-up connector set (1pcs) Black PV terminal (SOLXPOW X2-4~12K 1 pair / SOLXPOW X3-10~20K 2...
  • Page 15: Location

    SOLXPOW X2 Series & SOLXPOW X3 Series 3.3 Location The SOLXPOW X2 series and SOLXPOW X3 series inverters are designed with IP65 protection enclosure for indoor and outdoor installations. When selecting an inverter installation location, the following factors should be considered: 1.
  • Page 16 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 3.3.2 Installation Spacing Reserve enough clearance around the inverter to ensure sufficient space for heat dissipation. Figure 3-3 Spacing for installing an inverter 3.3.3 Installation Angle Install the inverter vertically. Never install the inverter horizontally, or at forward/backward tilted, or upside down.
  • Page 17: Mounting The Inverter

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 3.4 Mounting the Inverter 3.4.1 Wall Bracket Installation Dimensions of wall bracket (mm) Figure 3-5 Dimensions of wall bracket 1. Use the wall bracket as the template to mark the position of 5 holes on the wall.
  • Page 18 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Figure 3-7 Fixing the wall bracket 3.4.2 Mounting the Inverter Lift the inverter, hang the back rail on the fixed wall bracket carefully. Secure the inverter with M5 screws. Figure 3-8 Mounting the inverter 3.4.3 External Ground Connection...
  • Page 19 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series NOTICE ⚫ Reliable grounding is good for resisting surge voltage shock and improving EMI performance. ⚫ Inverters must be well-grounded. ⚫ For a system with only one inverter, just ground the PE cable.
  • Page 20: Electrical Connection

    ⚫ Do not use other brands or other types of terminals other than the terminals in the accessory package. PowMr has the right to refuse all damages caused by the mixed-use of terminals. ⚫ Moisture and dust can damage the inverter, ensure the cable gland is securely tightened during installation.
  • Page 21: Electrical Wiring Diagram

    SOLXPOW X2 Series & SOLXPOW X3 Series 4.1 Electrical Wiring Diagram This diagram shows SOLXPOW X2 series and SOLXPOW X3 series hybrid inverter wiring structure and composition, concerning the real project, the installation and wiring have to be in line with the local standards.
  • Page 22 AC supply can be isolated or switched. Figure 4-2 Standard wiring diagram *PowMr Smart Meter consists of ACR10R and SM. Define the cable connections for the meter based on the actual meter model and refer to Section 4.4. This cable diagram is for reference only.
  • Page 23 AS/NZS_3000. Otherwise, BACK-UP function will not work. Figure 4-3 Australia wiring diagram *PowMr Smart Meter consists of ACR10R and SM. Define the cable connections for the meter based on the actual meter model and refer to Section 4.4. This cable diagram is for reference only.
  • Page 24: Ac Connection

    ⚫ Before making the connection of AC cable, please confirm all DC & AC power source are disconnected from the inverter. ⚫ The PowMr SOLXPOW X2 series and SOLXPOW X3 series three-phase high voltage hybrid inverter applies to the three-phase power grid with a voltage of 230/400V and a frequency of 50/60Hz.
  • Page 25 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Residual Current Monitoring Device With an integrated universal residual current monitoring device, the inverter will disconnect immediately from the mains once a fault current with a value exceeding the limit is detected.
  • Page 26 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series WARNING ⚫ The cord end terminals must be locked tightly, and make sure it won’t be loose after a long period of use. 4. According to the arrow direction push the threaded sleeve to make it connected with the AC terminal head and then rotate the cable gland clockwise to lock it.
  • Page 27: Monitoring Device Installation

    4.3 Monitoring Device Installation PowMr SOLXPOW X2 series and SOLXPOW X3 series hybrid inverter supports WIFI, LAN, and 4G communication. Plug the WIFI, LAN, or 4G module into the COM1 port in the bottom of inverter. A slight "click"...
  • Page 28: Meter And Ct Connection

    PowMr CT cable with length of 2m, it’s fixed and can’t be extended. The CTs have been connected to the PowMr Meter when you received them, and you just need to follow the wiring diagram in the Meter to connect CT.
  • Page 29: Communication Connection

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Meter terminals definition as shown in table below: Definition Function ACR10R L1/L2/L3/N connect to grid to detect power grid voltage. L1-S1 L2-S2 L2-S1 To detect the CT current and direction. L2-S2...
  • Page 30 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Definition Function METER(RJ45-1) RS 485 Communicate with Meter BMS(RJ45-1) Communicate with BMS Multifunction Relay NO (Normally Open) Reserved Reserved DRM4/8 DRM3/7 DRM2/6 DRED For Australia and New Zealand DRM1/5 COM D/0...
  • Page 31 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 2. Take out the terminal block. Figure 4-14 3. Remove the seal and lead the cable through the cable gland. Figure 4-15 4.5.2 Connect the Meter And BMS Communication Cables NOTE ⚫...
  • Page 32 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 2. Insert one side of the RJ45 plug into the RJ45 port of terminal block. Figure 4-17 3. Insert another side of the communication cable into the meter RS485 port or BMS CAN port.
  • Page 33 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Figure 4-19 3. Fix all the wires to the terminal plug according to the assignment and tighten to a torque of 1.2+/-0.1N· m with a screwdriver. Figure 4-20 4. Pull the wires outward to check whether they are firmly installed. Insert the terminal block into the connector until it snaps into place with an audible click.
  • Page 34 ⚫ Before purchasing the battery, you need to make sure the battery you selected is in the battery approval list of PowMr, otherwise, the system may not work properly. Please contact your installer or PowMr service team for confirmation if you’re not sure about it.
  • Page 35 DRED (Demand Response Enabling Device) interface is special reserved for Australia and New Zealand according to their safety regulation, and PowMr doesn’t provide the DRED device for the customer. The inverter supports the demand response modes as specified in the standard AS/NZS 4777.
  • Page 36 CR (Ripple Control Receiver) interface is special reserved for Germany and some other European country according to their safety regulation, and PowMr doesn’t provide the RCR device for the customer. In Germany and some European areas, a ripple control receiver is used to convert a power grid dispatching signal to a dry contact signal.
  • Page 37 NOTICE ⚫ Maximum voltage and current at DO dry contact port: 230VAC 1A/30VDC 1A. NOTE ⚫ For more installation and setup information, please contact PowMr. Load Control Figure 4-27 Load control connection diagram...
  • Page 38 ⚫ The AC contactor should be placed between the inverter and the loads. ⚫ Do not connect the load to DO port directly. ⚫ The contactor is not supplied by the PowMr. Connect the load to the DO port of the inverter directly if the load is designed with a DI port.
  • Page 39 The on-grid and back-up side cannot be The back-up side cannot be connected on-grid connected to and generator directly. side or grid. For advanced applications, please contact our after-sales department. Figure 4-29 NOTE ⚫ For more installation and setup information about parallel system, please contact PowMr.
  • Page 40: Pv String Connection

    SOLXPOW X2 Series & SOLXPOW X3 Series 4.5.10 Fast stop PowMr SOLXPOW X2 series and SOLXPOW X3 hybrid inverter comes standard with fast stop function, and you can use this function by connecting an external switch into the fast stop interface if it requires in the installation place.
  • Page 41 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 4.6.1 PV Side Requirements System Layout of Units with external DC Switch 1. Local standards or codes may require PV systems that fit with an external DC switch on the DC side.
  • Page 42 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 1. Peel off the DC cable insulation sleeve for 7 mm. Figure 4-32 2. Disassemble the connector in the accessory bag. Figure 4-33 3. Insert the DC cable through the DC connector nut into the metal terminal and press the terminal with a professional crimping plier (pull back the cable with some power to check if the terminal is well connected to the cable).
  • Page 43 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 4.6.3 Installing the PV Connector 1. Rotate the DC switch to “OFF” position. Figure 4-36 2. Check the cable connection of the PV string for polarity correctness and ensure that the open circuit voltage in any case does not exceed the inverter input limit of 1,000V.PV Max.
  • Page 44: Power Cable Of The Battery Connection

    If the conductor core of the battery cable is too small, which may cause poor contact between the terminal and the cable, please use the cable specified in the above table, or contact PowMr to purchase terminals of other specifications.
  • Page 45 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 2. Disassemble the connector in the accessory bag. Figure 4-40 3. Insert the battery cable through the battery connector nut into the metal terminal and press the terminal with a professional crimping plier (pull back the cable with some power to check if the terminal is well connected to the cable).
  • Page 46 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series WARNING ⚫ Before making the battery connector, please make sure the polarity of the cable is correct. ⚫ Use a multimeter to measure the voltage of the battery pack and make sure the voltage is within the inverter limitation and the polarity is correct.
  • Page 47: Commissioning

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 5 Commissioning 5.1 App Preparation 1. Install the Local configuration App and Cloud monitoring App with latest version. Refer to "7.2 Cloud monitoring App and 7.3 Local configuration App". 2. Register an account on the Cloud monitoring App. If you have got the account and password from the distributor/installer or PowMr, skip this step.
  • Page 48: Stop The Inverter

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 5. Observe the LED indicator to ensure that the inverter operates normally. 6. After the inverter is started, please refer to the [QUICK USE GUIDE] which is attached to the access to configure the inverter.
  • Page 49: Operation

    ⚫ Please wait for 10 seconds and the inverter will automatically save your settings or modifications. 6.1 Operation Modes PowMr SOLXPOW X2 and SOLXPOW X3 Hybrid inverter has the following basic operation modes and you can configure the operation mode as per your preference in the App. General Mode...
  • Page 50 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Peak load Shifting (Load Shifting) Set the maximum power Pmax (kVA) contracted with the grid. When the load consumption is less than the Pmax, the PV will charge the battery first, and the grid supplies the load.
  • Page 51 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series UPS Mode In this working mode, the inverter will use the power from PV or grid to charge the battery until it is fully charged, and as long as the grid is there, the battery won’t discharge.
  • Page 52 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Economic Mode In this working mode, you can set charge/discharge power and time in the App, inverter will use the power from PV or grid (whether to use can be set in the App) to charge the battery in the predetermined period.
  • Page 53 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Off-grid Mode In the purely off-grid mode, power from PV will supply the back-up loads first and then charge the battery if there's surplus power. When the power from PV isn’t enough, the battery will discharge to supply back-up loads together with PV.
  • Page 54: Back-Up And Off-Grid Output

    4. Due to the condition of the battery itself, battery current might be limited by some factors, including but not limited to the temperature and weather. PowMr SOLXPOW X2 and SOLXPOW X3 hybrid inverter overloading ability in off-grid work mode describes as follows:...
  • Page 55: Main Window

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 6.3 Main Window Inverter working status: Waiting/Checking/On-Grid/Off-Grid/Fault Info/FW Updating Inverter Display Abbreviation and Complete Name Reference Table Abbreviation Complete Name V-Ipv1/2 PV input voltage and current of each MPPT Ppv1/2 PV input power of each MPPT...
  • Page 56: General Setting

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 6.4 General Setting...
  • Page 57 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Inverter Display Abbreviation and Complete Name Reference Table Abbreviation Complete Name System Info System information FM Version Firmware version Series number Fault Info Fault information RSSI Received signal strength indicator DHCP Set...
  • Page 58: Advanced Setting

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 6.5 Advanced Setting...
  • Page 59 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series...
  • Page 60 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Inverter Display Abbreviation and Complete Name Reference Table Abbreviation Complete Name Safety Set Select the code that meet local regulatory requirements Battery_ID Set Select the battery model Work Mode Current work mode / work mode setting...
  • Page 61: Country Code (Safety Code) Setting

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Abbreviation Complete Name System Maint. System maintenance, includes inverter stop and run, system restart In the multi-inverter parallel system, set the role of one inverter as the Multi-INV Role master and the other inverter as the slave.
  • Page 62 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Connect the AC cable, auto test will start after the inverter connected to the grid, see the operation steps below:...
  • Page 63: Reactive Power

    Figure 6-1 Capabilities This mode can be enabled via configuration software. It is enabled by default in some regions, such as AU, DE market. For information on how to change default setpoints please contact PowMr Technical Support at support@powmr.com. Descriptions of reactive power regulation mode:...
  • Page 64 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 6.8.3 “Qt” Mode In the Qt mode, system rated reactive power is fixed, and the system injects reactive power according to the delivered reactive power ratio. The setting range of the reactive power ratio is 0~60% or 0~-60%, corresponding to the ranges of inductive and capacitive reactive power regulation respectively.
  • Page 65 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 6.8.5 “Q(U)” Mode The reactive power output of the inverter will vary in response to the grid voltage. “Q(U)” Mode Parameter Descriptions: Parameter Explanation Range Hysteresis Ratio Voltage hysteresis ratio on the Q(U) mode curve...
  • Page 66: Monitoring

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 7 Monitoring 7.1 Monitoring Device Figure 7-1 Monitoring device display interface Indicator Status Description Connection abnormal. Always On Communicate with the server normally. The monitoring device is not connected to the router or is not connected to Slow flashing the base station.
  • Page 67: Cloud Monitoring App

    Otherwise, please refer to the [QUICK USE GUIDE] which is attached to the accessory bag. 7.2 Cloud monitoring App PowMr inverter provides a monitoring port that can collect and transmit data from the inverter to PowMr monitoring platform via an external monitoring device. Please refer to the product nameplate on side of enclosure to get the monitoring application.
  • Page 68: Technical Parameters

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 8 Technical Parameters 8.1 Table 1 Line Mode Specifications Model SOLXPOW X2-4K SOLXPOW X2-5K Line Mode Input voltage waveform Sinusoidal 8.0kVA 10.0kVA Max. input apparent power 3L/N/PE, 220/380V; 230/400V; 240/415V Rated AC voltage...
  • Page 69 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Model SOLXPOW X3-10K SOLXPOW X3-12K Line Mode Sinusoidal Input voltage waveform 20.0kVA 24.0kVA Max. input apparent power 3L/N/PE, 220/380V; 230/400V; 240/415V Rated AC voltage 50Hz/60Hz Rated AC frequency Max. input current 29.0A...
  • Page 70 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 8.2 Table 2: Inverter Mode Specifications (Backup Side) Model SOLXPOW X2-4K SOLXPOW X2-5K 4.0kW 5.0kW Rated output power 4.4kW 5.5kW Max. output power 4.0kVA 5.0kVA Rated output apparent power 4.4kVA 5.5kVA Max.
  • Page 71 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Model SOLXPOW X2-10K SOLXPOW X2-12K 10.0kW 12.0kW Rated output power 11.0kW 13.2kW Max. output power 10.0kVA 12.0kVA Rated output apparent power 11.0kVA 13.2kVA Max. output apparent power 14.5A 17.4A Rated output current 16.5A...
  • Page 72 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Model SOLXPOW X3-15K SOLXPOW X3-20K 15.0kW 20.0kW Rated output power 16.5kW 22.0kW Max. output power 15.0kVA 20.0kVA Rated output apparent power 16.5kVA 22.0kVA Max. output apparent power 21.7A 29.0A Rated output current 25.0A...
  • Page 73 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 8.3 Table 3 Specifications in Grid-Tie Mode (Grid-Side) Model SOLXPOW X2-4K SOLXPOW X2-5K 4.0kW 5.0kW Rated output power 4.4kW 5.5kW Max. output power 4.0kVA 5.0kVA Rated output apparent power 4.4kVA 5.5kVA Max.
  • Page 74 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Model SOLXPOW X2-10K SOLXPOW X2-12K 10.0kW 12.0kW Rated output power 11.0kW 13.2kW Max. output power 10.0kVA 12.0kVA Rated output apparent power 11.0kVA 13.2kVA Max. output apparent power 10.0kW 12.0kW Max. battery charging power 3L/N/PE, 220/380V;...
  • Page 75 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Model SOLXPOW X3-15K SOLXPOW X3-20K 15.0kW 20.0kW Rated output power 16.5kW 22.0kW Max. output power 15.0kVA 20.0kVA Rated output apparent power 16.5kVA 22.0kVA Max. output apparent power 15.0kW 20.0kW Max. battery charging power 3L/N/PE, 220/380V;...
  • Page 76 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 8.4 Table 4 Specifications in Charging Mode Model SOLXPOW X2-4K SOLXPOW X2-5K Battery specification Lithium Battery (with BMS) Battery type Battery communication mode 135-750V Battery voltage range Max. discharge current Utility or generator charging mode...
  • Page 77 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Model SOLXPOW X2-6K SOLXPOW X2-8K Battery specification Lithium Battery (with BMS) Battery type Battery communication mode 135-750V Battery voltage range Max. discharge current Utility or generator charging mode 3-Stage Charging algorithm Max.
  • Page 78 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Model SOLXPOW X2-10K SOLXPOW X2-12K Battery specification Lithium Battery (with BMS) Battery type Battery communication mode 135-750V Battery voltage range Max. discharge current Utility or generator charging mode 3-Stage Charging algorithm Max.
  • Page 79 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Model SOLXPOW X3-10K SOLXPOW X3-12K Battery specification Lithium Battery (with BMS) Battery type Battery communication mode 135-750V Battery voltage range Max. discharge current Utility or generator charging mode 3-Stage Charging algorithm Max.
  • Page 80 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Model SOLXPOW X3-15K SOLXPOW X3-20K Battery specification Lithium Battery (with BMS) Battery type Battery communication mode 135-750V Battery voltage range Max. discharge current Utility or generator charging mode 3-Stage Charging algorithm Max.
  • Page 81 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 8.5 Table 5 General Specifications Model SOLXPOW X2-4K SOLXPOW X2-5K PV: II; Main: III Surge Category 534*418*210mm (W*H*D) Dimensions 26kg Weight IP65 Protection Rating <15W Standby Power Consumption Transformerless Topology -30~60° C...
  • Page 82 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Model SOLXPOW X2-10K SOLXPOW X2-12K PV: II; Main: III Surge Category 534*418*210mm (W*H*D) Dimensions 26kg Weight IP65 Protection Rating <15W Standby Power Consumption Transformerless Topology -30~60° C Operating Temperature Range 0~100% Relative Humidity 3000m (>3000m derating)
  • Page 83 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Model SOLXPOW X3-15K SOLXPOW X3-20K PV: II; Main: III Surge Category 534*418*210mm (W*H*D) Dimensions 31kg Weight IP65 Protection Rating <15W Standby Power Consumption Transformerless Topology -30~60° C Operating Temperature Range 0~100% Relative Humidity 3000m (>3000m derating)
  • Page 84: Troubleshooting

    9 Troubleshooting 9.1 Error Message PowMr SOLXPOW X2 series and SOLXPOW X3 series hybrid inverter is designed in accordance with grid operation standards, and conform to the requirements of safety and EMC. The inverter had passed a series of rigorous tests to ensure it runs sustainably and reliably before shipment.
  • Page 85 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Error Message Description Solution 500 KΩ. 3. Seek help from the installer or manufacture. 1. Restart the inverter. 2. Check whether the PV panels, cables, The inverter detects that the and connectors are waterlogged or...
  • Page 86 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Error Message Description Solution Fail got failed. Neutral & ground between N&PE cable on AC side. If the cable are in poor connection voltage is higher than 10V, which on AC side.
  • Page 87: Protection

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series Error Message Description Solution 2. Check whether back-up side is short circuit. Internal communication got 1. Restart the inverter. SCI Fault failed. Caused by a strong 2. Seek for help from the installer or external magnetic field etc.
  • Page 88: Inverter Maintenance

    NOTICE ⚫ Any Arbitrary replacement of internal components is forbidden. ⚫ Please seek help from PowMr for maintenance support. Otherwise, we will not take any responsibility. NOTE ⚫ Please remember not to do the self-maintenance before being familiar with the proper instruction of the whole process.
  • Page 89: Battery Maintenance

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 9.4 Battery Maintenance Installation and maintenance of batteries should be performed or supervised with professional knowledge about batteries. Please contact your battery supplier for detailed installation and maintenance information. CAUTION ⚫ Do not dispose battery in fire, or it may explode.
  • Page 90: Contact Information

    User Manual SOLXPOW X2 Series & SOLXPOW X3 Series 10 Contact Information Should you have any question about this product, please contact us. We need the following information to provide you the best assistance: ⚫ Model of the device ⚫ Serial number of the device ⚫...
  • Page 91 User Manual SOLXPOW X2 Series & SOLXPOW X3 Series...