Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 1
INSTRUCTION MANUAL ECOSOFT
Filter media removes impurities from water. Rate of removal depends on the flow rate of
water going through the bed of media. Efficient purification requires that the flow rate is
within specified range (not too high or too low). Recommended range of flow rates per each
type of filter is listed in specifications in the end of this manual.

3. INSTALLATION

Installation area must meet all relevant building code. Water and power supply, and
ambient conditions must meet Specification requirements of this manual.
Observe all local plumbing and electrical code when connecting system to utilities
Install check valve when connecting the filter to water mains. Install second check valve
after the system to prevent back flow.
Particles such as sand, scale or rust can damage the control valve. Install a point-of-
entry sediment filter.
Equip the system with sampling taps and pressure gauges as shown on drawings. It will
help in case any maintenance or troubleshooting is necessary.
Install a vacuum relief valve as shown if there is a booster pump downstream of Ecosoft
filters. The FRP tanks may implode if subjected to negative pressure.
If your system does not include bypass valve assembly, run a bypass pipeline along the
entire system. This may be necessary for diagnostics and maintenance.
MEDIA SYSTEMS
®
9

Advertisement

Table of Contents
loading