V8 Mini R410A VRF 50Hz
Figure 3-8.8: M1 M2 communication wiring configuration – IDUs separate power supplied
L1+La+Lx≤200m, L11≤200mm.
ODU
M1
M2
N L
L1
Breaker
M1
M2
1# IDU
8.3.6 System X Y E and O A communication
The cross-sectional area of each core of the communication wiring is not less than 0.75 mm2, and the length must not
exceed 1200 m.
The centralized controller and digital electric meter are optional accessories. Please contact the local dealer for
purchase if needed.
Connect the shielding nets at both ends of the shielded wire to the sheet metal "
Applicable standards: EN 55014-1 and EN 55014-2. The communication line must be shielded wire.
Figure 3-8.9: X Y E and O A communication wiring configuration
Centralized controller
E
X Y
Refrigerant system 1#
Refrigerant system 2#
96
Communication wiring 2*1.5mm
La
· · ·
M1
M2
(2-9)# IDU
L
10# IDU
ODU
X Y E
P Q
E
O
A
P Q
E
L
N
P Q
Refrigerant shut-off
Device
ODU
X Y E
P Q
E
O
A
P Q
E
L
N
P Q
Refrigerant shut-off
Device
2
Lx
N L
Repeater 1
breaker
T O D O W N ID U
M1
M2
N
Digital Power Meter
A
O
...
3-(n-2)# IDU
L
N
E
IDU 1#
Digital Power Meter
O
A
...
3-(n-2)# IDU
L
N
E
IDU 1#
Communication wire
Power wire
M1
M2
T O U P ID U
L11
M1
M2
11# IDU
" of the electronic control box.
P Q
E
L
N
P Q
IDU (n-1)#
P Q
E
L
N
P Q
IDU (n-1)#
N L
Breaker
L
L
N
L
E
N
IDU n#
Resister
L
E
N
IDU n#
Resister