Electrical Characteristics - Midea MV8M-120WV2RN1 Engineering Data

Table of Contents

Advertisement

V8 Mini R410A VRF 50Hz

6 Electrical Characteristics

Table 2-6.1: Outdoor unit electrical characteristics
Model name
MV8M-120WV2RN1
MV8M-140WV2RN1
MV8M-160WV2RN1
Abbreviations:
MCA: Minimum Circuit Amps; TOCA: Total Over-current Amps; MFA: Maximum Fuse Amps; MSC: Maximum Starting Current (A); RLA: Rated Load Amps; FLA: Fan
Load Amps
Notes:
1. Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. Maximum allowable voltage
variation between phases is 2%.
2. Select wire size based on the value of MCA.
3. TOCA indicates the total overcurrent amps value of each OC set.
4. MFA is used to select overcurrent circuit breakers and residual-current circuit breakers.
5. MSC indicates the maximum current on compressor start-up in amps.
6. RLA is based on the following conditions: indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB
26
Power Supply
Min.
Max.
Hz
Volts
volts
volts
380-415
50
342
440
380-415
50
342
440
380-415
50
342
440
1
2
3
4
MCA
TOCA
MFA
MSC
(A)
(A)
(A)
(A)
14
13
20
/
15
14
20
/
17
15
20
/
Compressor
Fan Motor
5
6
RLA
Power
(A)
(kW)
10.4
0.2
11.4
0.2
12.9
0.2
FLA
(A)
0.6
0.6
0.6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

V8 seriesMv8m-140wv2rn1Mv8m-160wv2rn1

Table of Contents